§ 109.301. General monitoring requirements.

 The monitoring requirements established by the EPA under the National Primary Drinking Water Regulations, 40 CFR Part 141 (relating to national primary drinking water regulations), as of December 8, 1984, are incorporated by reference. Public water suppliers shall monitor for compliance with MCLs and MRDLs in accordance with the requirements established in the National Primary Drinking Water Regulations, except as otherwise established by this chapter unless increased monitoring is required by the Department under §  109.302 (relating to special monitoring requirements). Alternative monitoring require-ments may be established by the Department and may be implemented in lieu of monitoring requirements for a particular National Primary Drinking Water Regulation if the alternative monitoring requirements are in conformance with the Federal act and regulations. The monitoring requirements shall be applied as follows:

   (1)  Performance monitoring for filtration and disinfection. A public water supplier providing filtration and disinfection of surface water or GUDI sources shall conduct the performance monitoring requirements established by the EPA under the National Primary Drinking Water Regulations, unless increased monitoring is required by the Department under §  109.302.

     (i)   Except as provided under subparagraphs (ii) and (iii), a public water supplier:

       (A)   Shall determine and record the turbidity level of representative samples of the system’s filtered water at least once every 4 hours that the system is in operation, except as provided in clause (B).

       (B)   May substitute continuous turbidity monitoring and recording for grab sample monitoring and manual recording if it validates the continuous measurement for accuracy on a regular basis using a procedure specified by the manufacturer. For systems using slow sand filtration or filtration treatment other than conventional filtration, direct filtration or diatomaceous earth filtration, the Department may reduce sampling frequency to once per day.

       (C)   Shall continuously monitor and record the residual disinfectant concentration of the water being supplied to the distribution system and record both the lowest value for each day and the number of periods each day when the value is less than .2 mg/L for more than 4 hours. If a public water system’s continuous monitoring or recording equipment fails, the public water supplier may, upon notification of the Department under §  109.701(a)(3) (relating to reporting and recordkeeping), substitute grab sampling or manual recording every 4 hours in lieu of continuous monitoring. Grab sampling or manual recording may not be substituted for continuous monitoring or recording for longer than 5 days after the equipment fails.

       (D)   Shall measure and record the residual disinfectant concentration at representative points in the distribution system no less frequently than the frequency required for total coliform sampling for compliance with the MCL for microbiological contaminants.

     (ii)   For a public water supplier serving 3,300 or fewer people, the Department may reduce the residual disinfectant concentration monitoring for the water being supplied to the distribution system to a minimum of 2 hours between samples at the grab sampling frequencies prescribed as follows if the historical performance and operation of the system indicate the system can meet the residual disinfectant concentration at all times:

System Size (People) Samples/Day
‹500 1
500—1,000 2
1,001—2,500 3
2,501—3,300 4

     If the Department reduces the monitoring, the supplier shall nevertheless collect and analyze another residual disinfectant measurement as soon as possible, but no longer than 4 hours from any measurement which is less than .2 mg/L.

     (iii)   For a public water supplier serving fewer than 500 people, the Department may reduce the filtered water turbidity monitoring to one grab sample per day, if the historical performance and operation of the system indicate effective turbidity removal is maintained under the range of conditions expected to occur in the system’s source water.

     (iv)   A public water supplier providing conventional filtration treatment or direct filtration and serving 10,000 or more people and using surface water or GUDI sources shall, beginning January 1, 2002, conduct continuous monitoring of turbidity for each individual filter using an approved method under the EPA regulation in 40 CFR 141.74(a) (relating to analytical and monitoring requirements) and record the results at least every 15 minutes. Beginning January 1, 2005, public water suppliers providing conventional or direct filtration and serving fewer than 10,000 people and using surface water or GUDI sources shall conduct continuous monitoring of turbidity for each individual filter using an approved method under the EPA regulation in 40 CFR 141.74(a) and record the results at least every 15 minutes.

       (A)   The water supplier shall calibrate turbidimeters using the procedure specified by the manufacturer.

       (B)   If there is failure in the continuous turbidity monitoring equipment, the system shall conduct grab sampling every 4 hours in lieu of continuous monitoring.

       (C)   A public water supplier serving 10,000 or more persons has a maximum of 5 working days following the failure of the equipment to repair or replace the equipment before a violation is incurred.

       (D)   A public water supplier serving fewer than 10,000 persons has a maximum of 14 days following the failure of the equipment to repair or replace the equipment before a violation is incurred.

   (2)  Performance monitoring for unfiltered surface water and GUDI. A public water supplier using unfiltered surface water or GUDI sources shall conduct the following source water and performance monitoring requirements on an interim basis until filtration is provided, unless increased monitoring is required by the Department under §  109.302:

     (i)   Except as provided under subparagraphs (ii) and (iii), a public water supplier:

       (A)   Shall perform fecal coliform or total coliform density determinations on samples of the source water immediately prior to disinfection. Regardless of source water turbidity, the minimum frequency of sampling for fecal or total coliform determination may be no less than the following:

System Size (People) Samples/Week
‹500 1
500—3,299 2
3,300—10,000 3
10,001—25,000 4
25,001 or more 5

       (B)   Shall measure the turbidity of a representative grab sample of the source water immediately prior to disinfection at least once every 4 hours that the system is in operation, except as provided in clause (C).

       (C)   May substitute continuous turbidity monitoring for grab sample monitoring if it validates the continuous measurement for accuracy on a regular basis using a protocol approved by the Department.

       (D)   Shall continuously monitor the residual disinfectant concentration required under §  109.202(c)(1)(iii) (relating to State MCLs, MRDLs and treatment technique requirements) of the water being supplied to the distribution system and record the lowest value for each day. If a public water system’s continuous monitoring equipment fails, the public water supplier may, upon notification of the Department under §  109.701(a)(3), substitute grab sampling every 4 hours in lieu of continuous monitoring. Grab sampling may not be substituted for continuous monitoring for longer than 5 days after the equipment fails.

       (E)   Shall measure the residual disinfectant concentration at representative points in the distribution system no less frequently than the frequency required for total coliform sampling for compliance with the MCL for microbiological contaminants.

     (ii)   For a public water supplier serving 3,300 or fewer people, the Department may reduce the residual disinfectant concentration monitoring for the water being supplied to the distribution system to a minimum of 2 hours between samples at the grab sampling frequencies prescribed as follows if the historical performance and operation of the system indicate the system can meet the residual disinfectant concentration at all times:

System Size (People) Samples/Day
‹500 1
500—1,000 2
1,001—2,500 3
2,501—3,300 4

     If the Department reduces the monitoring, the supplier shall nevertheless collect and analyze another residual disinfectant measurement as soon as possible, but no longer than 4 hours from any measurement which is less than the residual disinfectant concentration approved under §  109.202(c)(1)(iii).

     (iii)   For a public water supplier serving fewer than 500 people, the Department may reduce the source water turbidity monitoring to one grab sample per day, if the historical performance and operation of the system indicate effective disinfection is maintained under the range of conditions expected to occur in the system’s source water.

   (3)  Monitoring requirements for coliforms. Public water systems shall determine the presence or absence of total coliforms for each routine or check sample; and, the presence or absence of fecal coliforms or E. coli for a total coliform positive sample in accordance with analytical techniques approved by the Department under §  109.304 (relating to analytical requirements). A system may forego fecal coliform or E. coli testing on a total coliform-positive sample if the system assumes that any total coliform-positive sample is also fecal coliform-positive. A system which chooses to forego fecal coliform or E. coli testing shall, under §  109.701(a)(3), notify the Department within 1 hour after the water system learns of the violation or the situation, and shall provide public notice in accordance with §  109.408 (relating to Tier 1 public notice—form, manner and frequency of notice).

     (i)   Frequency. Public water systems shall collect samples at regular time intervals throughout the monitoring period as specified in the system distribution sample siting plan under §  109.303(a)(2) (relating to sampling requirements). Systems which use groundwater and serve 4,900 persons or fewer, may collect all required samples on a single day if they are from different sampling sites in the distribution system.

       (A)   Except as provided under §  109.705(b) (relating to sanitary surveys), the number of monthly total coliform samples that community water systems shall take is based on the population served by the system as follows:

Minimum Number of
Population Served Samples per Month
25 to 1,000 1
1,001 to 2,500 2
2,501 to 3,300 3
3,301 to 4,100 4
4,101 to 4,900 5
4,901 to 5,800 6
5,801 to 6,700 7
6,701 to 7,600 8
7,601 to 8,500 9
8,501 to 12,900 10
12,901 to 17,200 15
17,201 to 21,500 20
21,501 to 25,000 25
25,001 to 33,000 30
33,001 to 41,000 40
41,001 to 50,000 50
50,001 to 59,000 60
59,001 to 70,000 70
70,001 to 83,000 80
83,001 to 96,000 90
96,001 to 130,000 100
130,001 to 220,000 120
220,001 to 320,000 150
320,001 to 450,000 180
450,001 to 600,000 210
600,001 to 780,000 240
780,001 to 970,000 270
970,001 to 1,230,000 300
1,230,001 to 1,520,000 330
1,520,001 to 1,850,000 360
1,850,001 to 2,270,000 390
2,270,001 to 3,020,000 420
3,020,001 to 3,960,000 450
3,960,001 or more 480

       (B)   Except as provided under §  109.705(c), the number of periodic total coliform samples that noncommunity water systems shall take is as follows:

         (I)   A noncommunity water system using only groundwater and serving 1,000 or fewer persons per day on a permanent basis, January through December each year, shall take one sample each calendar quarter that the system provides water to the public.

         (II)   A noncommunity water system using surface water (in total or in part) or serving more than 1,000 persons per day during a given month shall take the same number of samples as a community water system serving the same number of persons specified in clause (A) for each month the system provides water to the public, even if the population served is temporarily fewer than 1,000 persons per day. A groundwater system determined to be under the influence of surface water shall begin monitoring at this frequency 6 months after the Department determines that the source water is under the direct influence of surface water.

       (C)   A public water system that uses either a surface water or a GUDI source and does not practice filtration in compliance with Subchapter B (relating to MCLs, MRDLs or treatment technique requirements) shall collect at least one total coliform sample at the entry point, or an equivalent location as determined by the Department, to the distribution system within 24 hours of each day that the turbidity level in the source water, measured as specified in paragraph (2)(i)(B), exceeds 1.0 NTU. The Department may extend this 24-hour collection limit to a maximum of 72 hours if the system adequately demonstrates a logistical problem outside the system’s control in having the sample analyzed within 30 hours of collection. A logistical problem outside the system’s control may include a source water turbidity result exceeding 1.0 NTU over a holiday or weekend in which the services of a Department certified laboratory are not available within the prescribed sample holding time. These sample results shall be included in determining compliance with the MCL for total coliforms established under §  109.202(a)(2).

     (ii)   Repeat monitoring. A public water system shall collect a set of check samples within 24 hours of being notified of a total coliform-positive routine or check sample. The Department may extend this 24-hour collection limit to a maximum of 72 hours if the system adequately demonstrates a logistical problem outside the system’s control in having the check samples analyzed within 30 hours of collection. A logistical problem outside the system’s control may include a coliform-positive sample result received over a holiday or weekend in which the services of a Department certified laboratory are not available within the prescribed sample holding time.

       (A)   A system which collects more than one routine sample per monitoring period shall collect at least three check samples for each total coliform-positive sample found.

       (B)   A system which collects only one routine sample per monitoring period shall collect at least four check samples for each total coliform-positive sample found.

       (C)   The system shall collect at least one check sample from the sampling tap where the original total coliform-positive sample was taken, at least one check sample at a tap within five service connections upstream of the original coliform-positive sample and at least one check sample within five service connections downstream of the original sampling site. If a total coliform-positive sample occurs at the end of the distribution system or one service connection away from the end of the distribution system, the water supplier shall collect an additional check sample upstream of the original sample site in lieu of a downstream check sample.

       (D)   A system shall collect all check samples on the same day, except that a system with a single service connection may collect the required set of check samples all on the same day or consecutively over a 4-day period.

       (E)   If a check sample is total coliform-positive, the public water system shall collect additional check samples in the manner specified in this subparagraph. The system shall continue to collect check samples until either total coliforms are not detected in check samples, or the system determines that the MCL for total coliforms as established under §  109.202(a)(2) has been exceeded and notifies the Department.

       (F)   If a system collecting fewer than five routine samples per month has one or more valid total coliform-positive samples, the system shall collect at least five routine samples during the next month the system provides water to the public. The number of routine samples for the month following a total coliform-positive sample may be reduced by the Department to at least one sample the next month if the reason for the total coliform-positive sample is determined and the problem has been corrected or will be corrected before the end of the next month.

       (G)   Results of all routine and check samples not invalidated by the Department shall be included in determining compliance with the MCL for total coliforms as established under §  109.202(a)(2).

     (iii)   Invalidation of total coliform samples. A total coliform sample invalidated under this paragraph does not count towards meeting the minimum monitoring requirements of this section.

       (A)   The Department may invalidate a total coliform-positive sample if one of the following applies:

         (I)   The laboratory which performed the analysis establishes that improper sample analysis caused the total coliform-positive result.

         (II)   A domestic or other nondistribution system plumbing problem exists when a coliform contamination incident occurs that is limited to a specific service connection from which a coliform-positive sample was taken in a public water system with more than one service connection. The Department’s determination to invalidate a sample shall be based on a total coliform-positive check sample collected at the same tap as the original total coliform-positive sample and all total coliform-negative check samples collected within five service connections of the original total coliform positive sample. This type of sample invalidation does not apply to public water systems with only one service connection.

         (III)   A total coliform-positive sample result is due to a circumstance or condition which does not reflect water quality in the distribution system. The Department’s decision to invalidate a sample shall be based on evidence that the sample result does not reflect water quality in the distribution system. In this case, the system shall still collect all check samples required under subparagraph (ii) to determine compliance with the MCL for total coliforms as established under §  109.202(a)(2).

       (B)   A laboratory shall invalidate a total coliform sample if no total coliforms are detected and one of the following occurs:

         (I)   The sample produces a turbid culture in the absence of gas production using an analytical method where gas formation is examined.

         (II)   The sample exhibits confluent growth or produces colonies too numerous to count with an analytical method using a membrane filter.

       (C)   If a laboratory invalidates a sample because of interference as specified in clause (B), the laboratory shall notify the system within 1 business day to collect another sample from the same location as the original sample within 24 hours of being notified of the interference and have it analyzed for the presence of total coliforms. The system shall resample within 24 hours of being notified of interference and continue to resample every 24 hours until it receives a valid result. The Department may extend this 24-hour limit to a maximum of 72 hours if the system adequately demonstrates a logistical problem outside the system’s control in having the resamples analyzed within 30 hours. A logistical problem outside the system’s control may include a notification of a laboratory sample invalidation, due to interference, which is received over a holiday or weekend in which the services of a Department certified laboratory are not available within the prescribed sample holding time.

     (iv)   Special purpose samples, such as those taken to determine whether disinfection practices are sufficient following pipe placement, replacement or repair, may not be used to determine compliance with the MCL for total coliform. Check samples taken under subparagraph (ii) are not considered special purpose samples, and shall be used to determine compliance with the monitoring and MCL requirements for total coliforms established under this paragraph and §  109.202(a)(2).

   (4)  Exception. For a water system which complies with the performance monitoring requirements under paragraph (2), the monitoring requirements for compliance with the turbidity MCL do not apply.

   (5)  Monitoring requirements for VOCs. Community water systems and nontransient noncommunity water systems shall monitor for compliance with the MCLs for VOCs established by the EPA under 40 CFR 141.61(a) (relating to MCLs for organic contaminants). The monitoring shall be conducted according to the requirements established by the EPA under 40 CFR 141.24(f) (relating to organic chemicals other than total trihalomethanes, sampling and analytical requirements), incorporated herein by reference, except as modified by this chapter. Initial or first year monitoring mentioned in this paragraph refers to VOC monitoring conducted on or after January 1, 1993.

     (i)   Vinyl chloride. Monitoring for compliance with the MCL for vinyl chloride is required only for groundwater entry points at which one or more of the following two-carbon organic compounds have been detected: trichloroethylene, tetrachloroethylene, 1,2-dichloroethane, 1,1,1-trichloroethane, cis-1,2-dichloroethylene, trans-1,2-dichloroethylene or 1,1-dichloroethylene.

     (ii)   Initial monitoring schedule. The initial monitoring shall consist of four consecutive quarterly samples at each entry point in accordance with the following monitoring schedule during the compliance period beginning January 1, 1993, except for systems which are granted reduced initial monitoring in accordance with clauses (E) and (F). A system which monitors during the initial monitoring period, but begins monitoring before its scheduled initial monitoring year specified in this subparagraph, shall begin monitoring every entry point during the first calendar quarter of the year it begins monitoring, except as provided in clause (E).

       (A)   Systems serving more than 10,000 persons shall begin monitoring during the quarter beginning January 1, 1994.

       (B)   Systems serving 3,301 persons to 10,000 persons shall begin monitoring during the quarter beginning January 1, 1995.

       (C)   Systems serving 500 to 3,300 persons shall begin monitoring during the quarter beginning January 1, 1993.

       (D)   Systems serving fewer than 500 persons shall begin monitoring during the quarter beginning January 1, 1994.

       (E)   For systems serving 3,300 or fewer people which monitor at least one quarter prior to October 1, 1993, and do not detect VOCs at an entry point during the first quarterly sample, the required initial monitoring is reduced to one sample at that entry point. For systems serving 500 to 3,300 people to qualify for this reduced monitoring, the initial monitoring shall have been conducted during the quarter beginning January 1, 1993.

       (F)   For systems serving more than 3,300 people, which were in existence prior to January 1, 1993, initial monitoring for compliance with the MCLs for VOCs established by the EPA under 40 CFR 141.61(a) is reduced to one sample for each entry point which meets the following conditions:

         (I)   VOC monitoring required by the Department between January 1, 1988, and December 31, 1992, has been conducted and no VOCs regulated under 40 CFR 141.61(a) were detected.

         (II)   The first quarter monitoring required by this paragraph has been conducted during the first quarter of the system’s scheduled monitoring year under this paragraph, with no detection of a VOC.

       (G)   Initial monitoring of new entry points associated with new sources which are permitted under Subchapter E (relating to permit requirements) to begin operation after December 31, 1992, shall conduct initial monitoring as follows:

         (I)   Entry points at which a VOC is detected during new source monitoring shall be monitored quarterly beginning the first quarter the entry points begin serving the public. Quarterly monitoring shall continue until reduced monitoring is granted in accordance with subparagraph (iii)(D).

         (II)   Entry points at which no VOC is detected during new source monitoring shall begin initial quarterly monitoring during the first calendar quarter of the year after the entry point begins serving the public. If no VOC is detected during the first quarter of monitoring, first year monitoring is reduced to one sample at that entry point.

     (iii)   Repeat monitoring for entry points at which a VOC is detected.

       (A)   For entry points at which a VOC is detected at a level equal to or greater than its MCL during the first year of quarterly monitoring, the monitoring shall be repeated quarterly beginning the quarter following detection at a level equal to or greater than the MCL, for VOCs for which the EPA has established MCLs under 40 CFR 141.61(a), except for vinyl chloride as provided in subparagraph (i), until reduced monitoring is granted in accordance with clause (D).

       (B)   For entry points at which a VOC is detected, and reduced monitoring is granted in accordance with clause (D), and a VOC is thereafter detected at a level greater than the MCL, the monitoring shall be repeated quarterly beginning the quarter following detection at a level for the VOCs for which the EPA has established MCLs under 40 CFR 141.61(a), except for vinyl chloride as provided in subparagraph (i), until reduced monitoring is granted in accordance with clause (D).

       (C)   For entry points at which no VOC is detected during the first year of monitoring but a VOC is detected thereafter, the monitoring shall be repeated quarterly beginning the quarter following detection at a level for the VOCs for which the EPA has established MCLs under 40 CFR 141.61(a), except for vinyl chloride as provided in subparagraph (i), or until reduced monitoring is granted in accordance with clause (D).

       (D)   After analyses of four consecutive quarterly samples at an entry point, including initial quarterly samples, demonstrate that the VOC levels in each quarterly sample are less than the MCLs, the required monitoring is reduced to one sample per year at the entry point for the VOCs for which the EPA has established MCLs under 40 CFR 141.61(a), except for vinyl chloride as provided in subparagraph (i).

       (E)   A confirmation sample shall be collected and analyzed for each VOC listed under 40 CFR 141.61(a) which is detected at a level in excess of its MCL during annual or less frequent compliance monitoring. The confirmation sample shall be collected within 2 weeks of notification by the certified laboratory performing the analysis that an MCL has been exceeded. The average of the results of the original and the confirmation sample will be used to determine compliance. Monitoring shall be completed by the deadline specified for VOC compliance monitoring.

     (iv)   Repeat monitoring for entry points at which no VOC is detected.

       (A)   For entry points at which VOCs are not detected during the first year of quarterly monitoring, or annual monitoring if only one sample was required at an entry point for first year monitoring under subparagraph (ii)(E), (F) or (G)(II), required monitoring is reduced to one sample per entry point per year.

       (B)   For groundwater entry points where VOCs are monitored in accordance with this paragraph, but are not detected during 3 years of quarterly or annual monitoring, or both, required monitoring is reduced to one sample per entry point during each subsequent compliance period. Reduced monitoring shall be conducted at 3-year intervals from the year of required initial monitoring.

     (v)   Reduced monitoring. When reduced monitoring is provided under subparagraph (iii)(D), or subparagraph (iv)(A) or (B), the system shall monitor the entry point during the calendar year quarter of highest anticipated VOC levels or as specified by the Department. The reduced monitoring option in subparagraph (iv)(B) does not apply to entry points at which treatment has been installed for VOC removal. Quarterly performance monitoring is required for VOCs for which treatment has been installed.

     (vi)   Waivers. Waivers under 40 CFR 141.24(f) will not be available for the VOC monitoring requirements in this paragraph.

   (6)  Monitoring requirements for SOCs (pesticides and PCBs). Community water systems and nontransient noncommunity water systems shall monitor for compliance with the MCLs for SOCs established by the EPA under 40 CFR 141.61(c). The monitoring shall be conducted according to the requirements established by the EPA under 40 CFR 141.24(h), incorporated herein by reference except as modified by this chapter.

     (i)   Initial monitoring schedule. Initial monitoring shall consist of four consecutive quarterly samples at each entry point beginning during the quarter beginning January 1, 1995, except for systems which are granted an initial monitoring waiver in accordance with subparagraph (v). Systems which monitor during the initial monitoring period but begin monitoring before 1995 shall begin monitoring during the first calendar quarter of the year.

       (A)   New entry points associated with new sources which are vulnerable to SOC contamination, as determined in accordance with subparagraph (v), and which begin operation after March 31, 1995, and do not detect an SOC during new source sampling shall begin initial quarterly monitoring during the first calendar year quarter of the year after the entry point begins serving the public.

       (B)   New entry points associated with new sources which are vulnerable to SOC contamination as determined in accordance with subparagraph (v), at which an SOC is detected during new source sampling shall begin initial quarterly monitoring the first quarter the entry point begins serving the public. Quarterly monitoring shall continue until reduced monitoring is granted in accordance with subparagraph (ii)(E).

     (ii)   Repeat monitoring for SOCs that are detected. For entry points which were monitored for SOCs during the initial quarterly monitoring period or during the required quarterly monitoring immediately after being determined vulnerable to contamination by an SOC, repeat monitoring shall be conducted as follows:

       (A)   For entry points at which an SOC is detected at a level equal to or greater than its MCL, the monitoring for the detected SOC shall be continued quarterly, until reduced monitoring is granted in accordance with clause (E).

       (B)   For entry points at which an SOC is detected during the first year of quarterly monitoring, and reduced monitoring is granted in accordance with clause (E), and the SOC is thereafter detected at a level greater than its MCL, the monitoring for the detected SOC shall be repeated quarterly, until reduced monitoring is granted in accordance with clause (E).

       (C)   For entry points at which an SOC is not detected during the first year of quarterly monitoring, but an SOC is detected initially thereafter at a level less than the MCL, monitoring shall be repeated annually for the detected SOC.

       (D)   For entry points at which an SOC is not detected during the first year of quarterly monitoring, but the SOC is detected thereafter at a level equal to or greater than the MCL, monitoring for that SOC shall be repeated quarterly, until reduced monitoring is granted in accordance with clause (E).

       (E)   After analyses of four consecutive quarterly samples at an entry point, including initial quarterly samples, demonstrate that the SOC level in each quarterly sample is less than the MCL, the required monitoring for each SOC detected below the MCL is reduced to one sample per year at the entry point.

       (F)   For entry points at which either heptachlor or heptachlor epoxide is detected during the initial round of consecutive quarterly samples, or in subsequent repeat samples, the monitoring shall be continued for both contaminants in accordance with the more frequent monitoring required of the two contaminants based on the level at which each is detected.

       (G)   A confirmation sample shall be collected and analyzed for each SOC listed under 40 CFR 141.61(c) which is detected at a level in excess of its MCL during annual or less frequent compliance monitoring. The confirmation sample shall be collected within 2 weeks of the water supplier receiving notification from the certified laboratory performing the analysis that an MCL has been exceeded. The average of the results of the original and the confirmation samples will be used to determine compliance. Confirmation monitoring shall be completed by the deadline specified for SOC compliance monitoring.

     (iii)   Repeat monitoring for SOCs that are not detected. For entry points at which SOCs are not detected during the first year of quarterly monitoring, the required monitoring is reduced to one sample in each 3-year compliance period for systems serving 3,300 or fewer persons and to two consecutive quarterly samples in each compliance period for systems serving more than 3,300 persons. Reduced monitoring shall be conducted at 3-year intervals from the year of required initial VOC monitoring, in accordance with paragraph (5)(ii).

     (iv)   Reduced monitoring. When reduced monitoring is provided under subparagraph (ii) or (iii), the system shall monitor the entry point during the second calendar year quarter, or the second and third calendar year quarter when two quarterly samples are required in each compliance period, unless otherwise specified by the Department. The reduced monitoring option in subparagraph (iii) does not apply to entry points at which treatment has been installed for SOC removal. Compliance monitoring for SOCs for which treatment has been installed to comply with an MCL shall be conducted at least annually, and performance monitoring shall be conducted quarterly.

     (v)   Waivers. A waiver will be granted to a public water supplier from conducting the initial compliance monitoring or repeat monitoring, or both, for an SOC based on documentation provided by the public water supplier and a determination by the Department that the criteria in clause (B), (C) or (D) has been met. A waiver is effective for one compliance period and may be renewed in each subsequent compliance period. If the Department has not granted an areawide use waiver in accordance with clause (B), the public water supplier is responsible for submitting a waiver application and renewal application to the Department for review in accordance with clause (B) or (C) for specific entry points. Waiver applications will be evaluated relative to the vulnerability assessment area described in clause (A) and the criteria in clause (B) or (C). Entry points at which treatment has been installed to remove an SOC are not eligible for a monitoring waiver for the SOCs for which treatment has been installed.

       (A)   Vulnerability assessment area for SOCs except dioxin and PCBs.

         (I)   For groundwater entry points, the vulnerability assessment area shall consist of wellhead protection area Zones I and II.

         (II)   For surface water entry points, the vulnerability assessment area shall consist of the area that supplies water to the entry point and is separated from other watersheds by the highest topographic contour.

       (B)   Use waivers. An areawide use waiver will be granted by the Department for contaminants which the Department has determined have not been used, stored, manufactured or disposed of in this Commonwealth, or portions of this Commonwealth. A use waiver specific to a particular entry point requires that an SOC was not used, stored, manufactured or disposed of in the vulnerability assessment area. If use waiver criteria cannot be met, a public water supplier may apply for a susceptibility waiver.

       (C)   Susceptibility waivers. A susceptibility waiver for specific contaminants may be granted based on the following criteria, and only applies to groundwater entry points:

         (I)   Previous analytical results.

         (II)   Environmental persistence and transport of the contaminant.

         (III)   Proximity of the drinking water source to point or nonpoint source contamination.

         (IV)   Elevated nitrate levels as an indicator of the potential for pesticide contamination.

         (V)   Extent of source water protection or approved wellhead protection program.

       (D)   Waivers for dioxin and PCBs. A system is granted a waiver from monitoring for dioxin and PCBs unless the Department determines that there is a source of dioxin or PCB contamination which poses a threat to a drinking water source.

   (7)  Monitoring requirements for IOCs. Community water systems and nontransient noncommunity water systems shall monitor for compliance with the MCLs for IOCs established by the EPA under 40 CFR 141.62 (relating to maximum contaminant levels (MCLs) for inorganic contaminants), and for arsenic established by the EPA under 40 CFR 141.11 (relating to maximum contaminant levels for inorganic contaminants). Transient noncommunity water suppliers shall monitor for compliance with the MCLs for nitrate and nitrite. The monitoring shall be conducted according to the requirements established by the EPA under 40 CFR 141.23 (relating to inorganic chemical sampling and analytical requirements). The requirements are incorporated by reference except as modified by this chapter.

     (i)   Monitoring requirements for asbestos.

       (A)   Waivers for asbestos monitoring. A system is granted a waiver from asbestos monitoring unless the Department determines that the system’s distribution system contains asbestos cement pipe and the system has not implemented optimum corrosion control measures, or the Department determines that the system’s source water is vulnerable to asbestos contamination.

       (B)   Initial monitoring schedule. Community water systems and nontransient noncommunity water systems not granted a waiver under clause (A) shall monitor for compliance with the MCL for asbestos by taking one sample at each vulnerable sampling point during the first 3-year compliance period of each 9-year compliance cycle, with the initial compliance monitoring beginning not later than the calendar year beginning January 1, 1995.

       (C)   Monitoring of new entry points. New entry points which begin operation after December 31, 1995, shall conduct initial monitoring during the first compliance period of the first compliance cycle after the entry point begins serving the public, if the Department determines that a waiver cannot be granted in accordance with clause (A).

       (D)   Repeat monitoring for systems that detect asbestos. If a sample exceeds the MCL for asbestos, the monitoring at that sampling point shall be continued quarterly beginning in the quarter following the MCL violation. After four consecutive quarterly samples less than the MCL at that entry point, the required monitoring is reduced to one sample at that entry point during the first 3-year compliance period of each subsequent 9-year compliance cycle, if treatment has not been installed to remove asbestos from the source water. Compliance monitoring at entry points at which treatment has been installed to remove asbestos from source water shall be conducted at least annually, and performance monitoring shall be conducted quarterly.

     (ii)   Monitoring requirements for nitrate and nitrite. The following compliance monitoring for nitrite is not required at entry points receiving water which has been disinfected with free chlorine, chlorine dioxide or ozone:

       (A)   Initial monitoring schedule. A public water system shall begin new monitoring for nitrate and nitrite by taking one annual sample at each groundwater entry point to the system beginning during the year beginning January 1, 1993. Community water systems and nontransient noncommunity water systems with surface water sources shall monitor quarterly at each surface water entry point for nitrate and nitrite beginning during the quarter beginning January 1, 1993. Transient noncommunity water systems shall monitor each surface water entry point by taking one annual sample beginning during the year beginning January 1, 1993.

       (B)   Monitoring of new entry points. New community and nontransient noncommunity surface water entry points which begin serving the public after the first calendar quarter of a year and did not detect levels of nitrate or nitrite equal to or greater than 50% of the MCL during new source sampling shall begin initial monitoring for nitrate and nitrite during the first calendar quarter of the year after the entry point begins serving the public. New community and nontransient noncommunity groundwater and surface water entry points at which nitrate or nitrite is detected at levels equal to or greater than 50% of the MCL during new source sampling shall begin initial quarterly monitoring the first quarter the entry point begins serving the public. New community and nontransient noncommunity groundwater entry points at which nitrate and nitrite are not detected at levels equal to or greater than 50% of the MCL, and all transient noncommunity entry points, shall begin initial annual monitoring during the first new calendar year after the entry point begins serving the public.

       (C)   Repeat monitoring for systems with nitrate or nitrite levels equal to or greater than 50% of the MCL.

         (I)   For entry points at which initial monitoring results or subsequent monitoring indicate nitrate or nitrite levels equal to or greater than 50% of the MCL, community and nontransient noncommunity water systems shall begin quarterly monitoring the quarter following detection at that level and continue quarterly monitoring for both nitrate and nitrite, unless reduced monitoring is granted in accordance with subclause (III).

         (II)   For entry points at which initial monitoring results or subsequent monitoring indicate nitrate or nitrite levels greater than the MCL, transient noncommunity systems shall begin quarterly monitoring the quarter following detection at that level and continue quarterly monitoring for both nitrate and nitrite, unless reduced monitoring is granted in accordance with subclause (IV).

         (III)   After four consecutive quarterly samples at an entry point for a community or nontransient noncommunity system indicate nitrate and nitrite levels in each sample are less than 50% of the MCLs, the required compliance monitoring is reduced to one sample per year at the entry point. Annual monitoring shall be conducted during the calendar quarter in which the consecutive quarterly monitoring indicated that the highest levels of contamination were present, unless the Department determines that a different monitoring quarter should be used in accordance with paragraph (10).

         (IV)   After four consecutive quarterly samples at an entry point for a transient noncommunity system indicate nitrate and nitrite levels in each sample are less than the MCLs, the required compliance monitoring is reduced to one sample per year at the entry point. Annual monitoring shall be conducted during the calendar quarter in which the consecutive quarterly monitoring indicated that the highest levels of contamination were present, unless the Department determines that a different monitoring quarter should be used in accordance with paragraph (10).

         (V)   For nitrate or nitrite sample results in excess of the MCLs, the water supplier shall take a confirmation sample within 24 hours of having received the original sample result. A water supplier that is unable to comply with the 24-hour sampling requirement shall immediately notify persons served by the public water system in accordance with §  109.408. Systems exercising this option shall take and analyze a confirmation sample within 2 weeks of notification of the analytical results of the first sample.

         (VI)   Noncommunity water systems for which an alternate nitrate level has been approved by the Department in accordance with 40 CFR 141.11(d) are not required to collect a confirmation sample if only the nitrate MCL is exceeded and nitrate is not in excess of the alternate nitrate level. If the alternate nitrate level is exceeded, the water supplier shall collect a confirmation sample within 24 hours after being advised by the certified laboratory performing the analysis that the compliance sample exceeded 20 mg/L for nitrate. Confirmation monitoring shall be completed by the deadline for compliance monitoring. Quarterly performance monitoring is required for nitrate and nitrite at entry points where treatment has been installed to remove nitrate or nitrite.

       (D)   Repeat monitoring for systems with nitrate and nitrite levels less than 50% of the MCLs. For entry points at which initial monitoring results indicate nitrate and nitrite levels in each sample are less than 50% of the MCLs, nitrate and nitrite monitoring shall be repeated annually during the calendar quarter in which the water supplier anticipates the highest levels of contamination, unless the Department determines that a different monitoring quarter should be used in accordance with paragraph (10).

     (iii)   Monitoring requirements for antimony, arsenic, barium, beryllium, cadmium, cyanide, chromium, fluoride, mercury, nickel, selenium and thallium.

       (A)   Initial monitoring schedule. Community water systems and nontransient noncommunity water systems shall monitor each surface water entry point annually beginning during the year beginning January 1, 1993, and shall monitor each groundwater entry point once every 3 years beginning during the year beginning January 1, 1994.

       (B)   Monitoring of new entry points. New groundwater entry points which begin operation after December 31, 1994, shall begin initial monitoring in accordance with the schedule in clause (A)—that is, 1997, and so forth. New surface water entry points shall begin initial annual monitoring during the first new calendar year after the entry point begins serving the public.

       (C)   Repeat monitoring for entry points at which an IOC MCL is exceeded.

         (I)   For entry points at which initial monitoring results or subsequent monitoring indicates an IOC level in excess of the MCL, monitoring shall be repeated quarterly beginning the quarter following detection at that level for each IOC in excess of an MCL, until reduced monitoring is granted in accordance with subclause (II).

         (II)   After analyses of four consecutive quarterly samples at an entry point where treatment has not been installed to comply with an IOC MCL indicate that contaminant levels are less than the MCLs, the required monitoring for each IOC less than the MCL is reduced to the frequencies stated in clause (A). This reduced monitoring option does not apply to entry points at which treatment has been installed for IOC removal. Compliance monitoring for IOCs for which treatment has been installed to comply with an MCL shall be conducted at least annually, and performance monitoring shall be conducted quarterly.

         (III)   A confirmation sample shall be collected and analyzed for each IOC listed under 40 CFR 141.11(b) or 141.62(b) which is detected at a level in excess of its MCL during annual or less frequent compliance monitoring. The confirmation sample shall be collected within 2 weeks of notification by the certified laboratory performing the analysis that an MCL has been exceeded. The average of the results of the original and the confirmation samples will be used to determine compliance. Confirmation monitoring shall be completed by the deadline specified for IOC compliance monitoring.

       (D)   Waivers for IOC monitoring. Except when treatment has been installed to remove the IOC, after three consecutive rounds of quarterly, annual or triennial monitoring indicate the contaminant level for an IOC is below the MCL in all samples at an entry point, routine monitoring for the remainder of the compliance cycle for that IOC is waived and the required monitoring for the IOC is reduced to one sample per 9-year compliance cycle at that entry point. Reduced monitoring shall be conducted during the first monitoring period of the next monitoring cycle. A waiver is effective for one compliance cycle and may be renewed in each subsequent compliance cycle.

       (E)   Operational monitoring for fluoride. Public water suppliers who fluoridate shall conduct operational monitoring for fluoride daily.

   (8)  Monitoring requirements for public water systems that obtain finished water from another public water system.

     (i)   Consecutive water suppliers shall monitor for compliance with the MCL for microbiological contaminants at the frequency established by the EPA and incorporated by reference into this chapter.

     (ii)   Community consecutive water suppliers shall:

       (A)   Monitor for compliance with the MCL for TTHMs established under 40 CFR 141.12 (relating to maximum contaminant levels for total trihalomethanes) in accordance with 40 CFR 141.30 (relating to total trimalomethanes sampling, analytical and other requirements) if the system does one of the following:

         (I)   Serves more than 10,000 persons.

         (II)   Obtains finished water from another public water system serving more than 10,000 persons.

       (B)   Monitor the distribution system for compliance with the MCL for asbestos at the frequency indicated in paragraph (7)(i), when the Department determines that the system’s distribution system contains asbestos cement pipe and optimum corrosion control measures have not been implemented.

     (iii)   Consecutive water suppliers are exempt from conducting monitoring for the MCLs for VOCs, SOCs and IOCs and radionuclides if the public water system from which the finished water is obtained complies with paragraphs (5)—(7) and (14), except that asbestos monitoring is required in accordance with subparagraph (ii)(B).

     (iv)   For a public water system which is not a consecutive water system, the exemption in subparagraph (iii) applies to entry points which obtain finished water from another public water system.

     (v)   A public water supplier that obtains finished water from another permitted public water system using either surface water or GUDI sources shall, beginning May 16, 1992, measure the residual disinfectant concentration at representative points in the distribution system at least as frequently as the frequency required for total coliform sampling for compliance with the MCL for microbiological contaminants.

     (vi)   Community water systems and nontransient noncommunity water systems that obtain finished water from another permitted public water system shall comply with the monitoring requirements for disinfection byproducts and disinfectant residuals in paragraphs (12)(i)—(iii) and (13).

   (9)  Monitoring requirements for POE devices. A public water supplier using a POE device shall, in addition to the monitoring requirements specified in paragraphs (1)—(8), conduct monitoring on the devices installed. As a minimum, the monitoring shall include the MCLs for which the POE device is intended to treat and monthly microbiological monitoring. The Department may allow the water supplier to reduce the frequency of microbiological monitoring based upon historical performance. Except for microbiological contaminants, monitoring shall be performed quarterly on 25% of the installed POE devices with the locations rotated so that each device is monitored at least once annually, unless increased monitoring is required by the Department under §  109.302.

   (10)  Additional monitoring. The Department may by written notice require a public water supplier to conduct monitoring for compliance with MCLs or MRDLs during a specific portion of a monitoring period, if necessary to ensure compliance with the monitoring or reporting requirements in this chapter.

   (11)  Monitoring requirements for entry points that do not provide water continuously. Entry points from which water is not provided during every quarter of the year shall monitor in accordance with paragraphs (5)—(7), except that monitoring is not required during a quarter when water is not provided to the public, unless special monitoring is required by the Department under §  109.302.

   (12)  Monitoring requirements for disinfection byproducts and disinfection byproduct precursors. Community water systems and nontransient noncommunity water systems that use a chemical disinfectant or oxidant shall monitor for disinfection byproducts and disinfection byproduct precursors in accordance with this paragraph. Community water systems and nontransient noncommunity water systems that obtain finished water from another public water system that uses a chemical disinfectant or oxidant to treat the finished water shall monitor for TTHMs and HAA5 in accordance with this paragraph. Systems that use either surface water or GUDI sources and that serve at least 10,000 persons shall begin monitoring by January 1, 2002. Systems that use either surface water or GUDI sources and that serve fewer than 10,000 persons, or systems that use groundwater sources, shall begin monitoring by January 1, 2004. Systems monitoring for disinfection byproducts and disinfection byproduct precursors shall take all samples during normal operating conditions. Systems monitoring for disinfection byproducts and disinfection byproduct precursors shall use only data collected under this chapter to qualify for reduced monitoring. Compliance with the MCLs and monitoring requirements for TTHMs, HAA5, chlorite (where applicable) and bromate (where applicable) shall be determined in accordance with 40 CFR 141.132 and 141.133 (relating to monitoring requirements; and compliance requirements) which are incorporated herein by reference.

     (i)   TTHMs and HAA5.

       (A)   Routine monitoring.

         (I)   Systems that use either surface water or GUDI sources shall monitor as follows:

           (-a-)   Systems serving at least 10,000 persons shall take at least four samples per quarter per treatment plant. At least 25% of all samples collected each quarter shall be collected at locations representing maximum residence time. The remaining samples shall be taken at locations that are representative of at least average residence time and that are representative of the entire distribution system, taking into account the number of persons served, the different sources of water, and the different treatment methods.

           (-b-)   Systems serving from 500 to 9,999 persons shall take at least one sample per quarter per treatment plant. The sample shall be taken at a location that represents a maximum residence time.

           (-c-)   Systems serving fewer than 500 persons shall take at least one sample per year per treatment plant during the month of warmest water temperature. The sample shall be taken at a location that represents a maximum residence time. If the sample, or average of all samples, exceeds either a TTHM or HAA5 MCL, then the system shall take at least one sample per quarter per treatment plant beginning in the quarter immediately following the quarter in which the system exceeds either the TTHM or HAA5 MCL. The sample shall be taken at a location that represents a maximum residence time. If, after at least 1 year of monitoring, the TTHM running annual average is no greater than 0.060 mg/L and the HAA5 running annual average is no greater than 0.045 mg/L, the required monitoring is reduced back to one sample per year per treatment plant.

           (-d-)   If a system samples more frequently than the minimum required in items (-a-)—(-c-), at least 25% of all samples collected each quarter shall be collected at locations representing maximum residence time, with the remainder of the samples representing locations of at least average residence time.

         (II)   Systems that use only groundwater sources not included under subclause (I) shall monitor as follows:

           (-a-)   Systems serving at least 10,000 persons shall take at least one sample per quarter per treatment plant. Multiple wells drawing water from a single aquifer may be considered as a single treatment plant. The sample shall be taken at a location that represents a maximum residence time.

           (-b-)   Systems serving fewer than 10,000 persons shall take at least one sample per year per treatment plant during the month of warmest water temperature. Multiple wells drawing water from a single aquifer may be considered as a single treatment plant. The sample shall be taken at a location that represents a maximum residence time. If the sample, or average of all samples, exceeds either a TTHM or HAA5 MCL, then the system shall take at least one sample per quarter per treatment plant beginning in the quarter immediately following the quarter in which the system exceeds either the TTHM or HAA5 MCL. The sample shall be taken at a location that represents a maximum residence time. If, after at least 1 year of monitoring, the TTHM running annual average is no greater than 0.060 mg/L and the HAA5 running annual average is no greater than 0.045 mg/L, the required monitoring is reduced back to one sample per year per treatment plant.

           (-c-)   If a system samples more frequently than the minimum required, at least 25% of all samples collected each quarter shall be collected at locations representing maximum residence time, with the remainder of the samples representing locations of at least average residence time.

       (B)   Reduced monitoring. Systems shall monitor for TTHMs and HAA5 for at least 1 year prior to qualifying for reduced monitoring. Systems serving at least 500 persons and that use either surface water or GUDI sources shall monitor source water TOC monthly for at least 1 year prior to qualifying for reduced monitoring. The Department retains the right to require a system that meets the requirements of this clause to resume routine monitoring.

         (I)   For systems serving at least 500 persons that use either surface water or GUDI sources and that have a source water TOC running annual average that is no greater than 4.0 mg/L, a TTHM running annual average that is no greater than 0.040 mg/L and an HAA5 running annual average that is no greater than 0.030 mg/L, the required monitoring is reduced according to items (-a-) and (-b-). Systems serving at least 10,000 persons shall resume routine monitoring as prescribed in clause (A) if the TTHM running annual average exceeds 0.060 mg/L or the HAA5 running annual average exceeds 0.045 mg/L. Systems serving from 500 to 9,999 persons shall resume routine monitoring as prescribed in clause (A) if the annual TTHM average exceeds 0.060 mg/L or the annual HAA5 average exceeds 0.045 mg/L. Systems serving at least 500 persons that must resume routine monitoring shall resume routine monitoring in the quarter immediately following the quarter in which the system exceeded the specified TTHM or HAA5 criteria.

           (-a-)   For systems serving at least 10,000 persons, the required monitoring is reduced to one sample per quarter per treatment plant. The sample shall be taken at a location that represents a maximum residence time.

           (-b-)   For systems serving from 500 to 9,999 persons, the required monitoring is reduced to one sample per year per treatment plant. The sample shall be taken during the month of warmest water temperature and at a location that represents a maximum residence time.

         (II)   For systems that use only groundwater sources not included under subclause (I), the required monitoring is reduced according to the following:

           (-a-)   For systems serving at least 10,000 persons that have a TTHM running annual average that is no greater than 0.040 mg/L and an HAA5 running annual average that is no greater than 0.030 mg/L, the required monitoring is reduced to one sample per year per treatment plant. The sample shall be taken during the month of warmest water temperature and at a location that represents a maximum residence time. If the annual TTHM average exceeds 0.060 mg/L or the annual HAA5 average exceeds 0.045 mg/L, the system shall resume routine monitoring as prescribed in clause (A) in the quarter immediately following the quarter in which the system exceeds 0.060 mg/L for TTHMs or 0.045 mg/L for HAA5.

           (-b-)   For systems serving fewer than 10,000 persons that have an annual TTHM average that is no greater than 0.040 mg/L and an annual HAA5 average that is no greater than 0.030 mg/L for 2 consecutive years or an annual TTHM average that is no greater than 0.020 mg/L and an annual HAA5 average that is no greater than 0.015 mg/L for 1 year, the required monitoring is reduced to one sample per 3-year cycle per treatment plant. The sample shall be taken at a location that represents a maximum residence time during the month of warmest water temperature. The 3-year cycle shall begin on January 1 following the quarter in which the system qualifies for reduced monitoring. If the TTHM average exceeds 0.060 mg/L or the HAA5 average exceeds 0.045 mg/L, the system shall resume routine monitoring as prescribed in clause (A), except that systems that exceed either a TTHM or HAA5 MCL shall increase monitoring to at least one sample per quarter per treatment plant beginning in the quarter immediately following the quarter in which the system exceeds the TTHM or HAA5 MCL.

     (ii)   Chlorite. Community water systems and nontransient noncommunity water systems that use chlorine dioxide for disinfection or oxidation shall monitor for chlorite.

       (A)   Routine monitoring.

         (I)   Daily monitoring. Systems shall take daily samples at the entrance to the distribution system. Systems that must conduct additional monitoring in accordance with clause (B) shall continue to take routine daily samples at the entrance to the distribution system.

         (II)   Monthly monitoring.

           (-a-)   Systems shall take a three-sample set each month in the distribution system. The system shall take one sample at each of the following locations:

            (-1-)   As close to the first customer as possible.

            (-2-)   At a location representing an average residence time.

            (-3-)   At a location representing a maximum residence time.

           (-b-)   Systems that must conduct additional monitoring in accordance with subclause (III) may use the results of the additional monitoring to meet the monthly monitoring requirements of this subclause.

         (III)   Additional monitoring. If a daily sample at the entrance to the distribution system exceeds the chlorite MCL, the system shall take three samples in the distribution system on the following day. The system shall take one sample at each of the following locations:

           (-a-)   As close to the first customer as possible.

           (-b-)   At a location representing an average residence time.

           (-c-)   At a location representing a maximum residence time.

       (B)   Reduced monitoring. Chlorite monitoring in the distribution system required by clause (A)(II) is reduced to one three-sample set per quarter after 1 year of monitoring where no individual chlorite sample taken in the distribution system under clause (A)(II) has exceeded the chlorite MCL and the system has not been required to conduct additional monitoring under clause (A)(III). If any of the three individual chlorite samples taken quarterly in the distribution system exceeds the chlorite MCL or the system is required to conduct additional monitoring under clause (A)(III), the system shall revert to routine monitoring as prescribed by clause (A).

     (iii)   Bromate. Community water systems and nontransient noncommunity water systems that use ozone for disinfection or oxidation shall monitor for bromate.

       (A)   Routine monitoring. Systems shall take one sample per month for each treatment plant that uses ozone. Systems shall take the monthly sample at the entrance to the distribution system while the ozonation system is operating under normal conditions.

       (B)   Reduced monitoring. For systems that have an average source water bromide concentration that is less than 0.05 mg/L based upon representative monthly bromide measurements for 1 year, the required monitoring is reduced from monthly to quarterly. Systems on reduced monitoring shall continue to take monthly samples for source water bromide. If the running annual average source water bromide concentration, computed quarterly, equals or exceeds 0.05 mg/L based upon representative monthly measurements, the system shall revert to routine monitoring as prescribed by clause (A).

     (iv)   Disinfection byproduct precursors. Community water systems and nontransient noncommunity water systems that use either surface water or GUDI sources and that use conventional filtration shall monitor for disinfection byproduct precursors.

       (A)   Routine monitoring. Systems shall take monthly samples of the source water alkalinity, the source water TOC and postsedimentation TOC for each treatment plant that uses conventional filtration. Postsedimentation TOC can be taken at any point between sedimentation effluent and the entry point to the distribution system. The three samples shall be taken concurrently and at a time that is representative of both normal operating conditions and influent water quality.

       (B)   Reduced monitoring. For systems with an average postsedimentation TOC of less than 2.0 mg/L for 2-consecutive years, or less than 1.0 mg/L for 1 year, the required monitoring for source water alkalinity, source TOC and postsedimentation TOC is reduced from monthly to quarterly for each applicable treatment plant. The system shall revert to routine monitoring as prescribed by clause (A) in the month following the quarter when the annual average postsedimentation TOC is not less than 2.0 mg/L.

       (C)   Early monitoring. Systems may begin monitoring to determine whether the TOC removal requirements of 40 CFR 141.135(b)(1) (relating to enhanced coagulation and enhanced softening performance requirements) can be met 12 months prior to the compliance date for the system. This monitoring is not required and failure to monitor during this period is not a violation. However, any system that does not monitor during this period, and then determines in the first 12 months after the compliance date that it is not able to meet the requirements of 40 CFR 141.135(b)(1) and shall therefore apply for alternate minimum TOC removal requirements under 40 CFR 141.135(b)(4) is not eligible for retroactive approval of the alternate minimum TOC removal requirements and is in violation. Systems may apply for alternate minimum TOC removal requirements any time after the compliance date.

   (13)  Monitoring requirements for disinfectant residuals. Community water systems and nontransient noncommunity water systems that use either chlorine, chloramines or chlorine dioxide shall monitor for disinfectant residuals in accordance with this paragraph. Community water systems and nontransient noncommunity water systems that obtain finished water from another public water system that uses either chlorine or chlorine dioxide to treat the finished water shall monitor for chlorine residual in accordance with this paragraph. Community water systems and nontransient noncommunity water systems that obtain finished water from another public water system that uses chloramines to treat the finished water shall monitor for chloramine residual in accordance with this paragraph. Transient noncommunity water systems that use chlorine dioxide as either a disinfectant or oxidant shall monitor for chlorine dioxide residual in accordance with this paragraph. Systems that use either surface water or GUDI sources and that serve at least 10,000 persons shall begin monitoring by January 1, 2002. Systems that use either surface water or GUDI sources and that serve fewer than 10,000 persons, or systems that use groundwater sources, shall begin monitoring by January 1, 2004. Systems monitoring for disinfectant residuals shall take all samples during normal operating conditions. Compliance with the MRDLs and monitoring requirements for chlorine, chloramines and chlorine dioxide (where applicable) shall be determined in accordance with 40 CFR 141.132 and 141.133 (relating to monitoring requirements; and compliance requirements) which are incorporated herein by reference.

     (i)   Chlorine and chloramines. Systems shall measure the residual disinfectant level at the same points in the distribution system and at the same time that total coliforms are sampled, as specified in paragraph (3). Systems that used either surface water or GUDI sources may use the results of residual disinfectant concentration sampling conducted under paragraph (1) or (2) in lieu of taking separate samples.

     (ii)   Chlorine dioxide.

       (A)   Routine monitoring. Systems shall take one sample per day at the entrance to the distribution system. For any daily sample that exceeds the MRDL, the system shall conduct additional monitoring as specified in clause (B) in addition to the sample required at the entrance to the distribution system.

       (B)   Additional monitoring. If a daily sample at the entrance to the distribution system exceeds the chlorine dioxide MRDL, the system shall take three samples in the distribution system on the following day. If chlorine dioxide or chloramines are used to maintain a disinfectant residual in the distribution system, or if chlorine is used to maintain a disinfectant residual in the distribution system and there are no disinfectant addition points after the entrance to the distribution system, the system shall take three samples as close to the first customer as possible, at intervals of at least 6 hours. If chlorine is used to maintain a disinfectant residual in the distribution system and there are one or more disinfection addition points after the entrance to the distribution system, the system shall take one sample at each of the following locations:

         (I)   As close to the first customer as possible.

         (II)   At a location representing an average residence time.

         (III)   At a location representing a maximum residence time.

   (14)  Monitoring requirements for radionuclides. Community water systems shall monitor for compliance with the MCLs for radionuclides established by the EPA under 40 CFR 141.66(b), (c), (d) and (e) (relating to maximum contaminant levels for radionuclides). The monitoring shall be conducted according to the requirements established by EPA under 40 CFR 141.25 and 141.26 (relating to analytical methods for radioactivity; and compliance requirements for radionuclides in community water systems) which are incorporated by reference, except as modified by this chapter. Initial or first-year monitoring mentioned in this paragraph refers to monitoring conducted on or after January 1, 2005.

     (i)   Monitoring requirements for gross alpha particle activity, radium-226, radium-228 and uranium.

       (A)   Initial monitoring schedule. The initial monitoring shall consist of four consecutive quarterly samples for each radionuclide at each entry point in accordance with the following monitoring schedule except for systems that are granted reduced initial monitoring in accordance with subclause (V).

         (I)   Systems serving more than 3,301 persons shall begin monitoring during the quarter beginning January 1, 2005.

         (II)   Systems serving 500 to 3,300 persons shall begin monitoring during the quarter beginning January 1, 2006.

         (III)   Systems serving fewer than 500 persons shall begin monitoring during the quarter beginning January 1, 2007.

         (IV)   Systems that add new entry points associated with new sources shall begin initial quarterly monitoring during the first quarter the entry point begins serving the public. Quarterly monitoring shall continue until reduced monitoring is granted in accordance with clause (B) or subclause (V).

         (V)   If the first 2 quarterly samples for a radionuclide at an entry point have results below the detection limit, as defined in 40 CFR 141.25(c)(1), the final two quarterly samples for that radionuclide at that entry point are waived.

         (VI)   For entry points at which the monitoring result for a radionuclide at an entry point is above the MCL, the system shall collect and analyze quarterly samples for that radionuclide at that entry point until the system has results from 4 consecutive quarters for that radionuclide at that entry point that are at or below the MCL.

       (B)   Repeat monitoring. Beginning with the January 1, 2008, compliance period, systems shall take one sample for each radionuclide at each entry point in each 3-year compliance period, unless the system qualifies for reduced monitoring as follows:

         (I)   For entry points where the average of the initial monitoring results for a radionuclide is at or above the detection limit as defined in 40 CFR 141.25(c)(1), but at or below one-half of the MCL for that radionuclide, the repeat monitoring is reduced to one sample for that radionuclide at that entry point every 6 years.

         (II)   For entry points where the average of the initial monitoring results for a radionuclide is below the detection limit as defined in 40 CFR 141.25(c)(1), the repeat monitoring is reduced to one sample for that radionuclide at that entry point every 9 years.

         (III)   If a system has a monitoring result that exceeds the MCL for a radionuclide, the system shall collect and analyze quarterly samples for that radionuclide at that entry point beginning the next calendar quarter following the exceedance until the system has results from 4 consecutive quarters for that radionuclide at that entry point that are below the MCL.

         (IV)   Systems shall use the results of the samples collected during the repeat monitoring period to determine the monitoring frequency for subsequent monitoring periods.

         (V)   Reduced monitoring does not apply to those systems where treatment has been installed for radionuclide removal to comply with an MCL listed under 40 CFR 141.66. Compliance monitoring for radionuclides where treatment has been installed to comply with an MCL shall be conducted at least annually, and performance monitoring for the specific radionuclides for which treatment is provided shall be conducted quarterly.

       (C)   Gross alpha substitution. A gross alpha particle activity measurement may be substituted for the required radium-226 measurement provided that the measured gross alpha particle activity does not exceed 5 pCi/L. A gross alpha particle activity measurement may be substituted for the required uranium measurement provided that the measured gross alpha particle activity does not exceed 15 pCi/L. The gross alpha measurement shall have a confidence interval of 95% (1.65, where is the standard deviation of the net counting rate of the sample) for radium-226 and uranium. If the gross alpha particle activity result is less than the detection limit as defined in 40 CFR 141.25(c)(1), one-half of the detection limit will be used to determine compliance and the future monitoring frequency.

       (D)   Grandfathering. The Department will allow appropriate historical data collected at an entry point to satisfy the initial monitoring requirements required under clause (A) for that entry point in the following situations:

         (I)   A system having only one entry point may use the monitoring data from the compliance monitoring period between June 2000 and December 8, 2003.

         (II)   A system with multiple entry points and having appropriate historical data for each entry point may use the monitoring data from the compliance monitoring period between June 2000 and December 8, 2003.

         (III)   A system with multiple entry points and having appropriate historical data for a representative point in the distribution system may use the monitoring data from the compliance monitoring period between June 2000 and December 8, 2003, provided that the Department finds that the appropriate historical data satisfactorily demonstrate that each entry point is expected to be in compliance based upon the appropriate historical data and reasonable assumptions about the variability of radionuclide levels between entry points. The system shall supply sufficient information to allow the Department to make a written finding indicating how the data conform to these requirements.

     (ii)   Monitoring requirements for beta-particle and photon radioactivity.

       (A)   Systems designated by the Department as vulnerable to beta-particle or photon radioactivity, or both, shall sample for beta particle and photon radioactivity. Systems shall collect quarterly samples for beta emitters and annual samples for tritium and strontium-90 at each entry point, beginning within 1 quarter after being notified by the Department.

         (I)   If the gross beta particle activity minus the naturally occurring potassium-40 beta particle activity at an entry point has a running annual average (computed quarterly) less than or equal to 50 pCi/L (screening level), the frequency of monitoring at that entry point shall be repeated every 3 years. Systems shall collect all samples required in clause (A) during the reduced monitoring period.

         (II)   For systems in the vicinity of a nuclear facility, the system may utilize environmental surveillance data collected by the nuclear facility in lieu of monitoring at the system’s entry points, when the Department determines that the data is applicable to the system. If there is a release from a nuclear facility, systems that are using surveillance data shall begin monitoring at the community water system’s entry points in accordance with clause (A).

       (B)   Systems designated by the Department as utilizing waters contaminated by effluents from nuclear facilities shall sample for beta particle and photon radioactivity. Systems shall monitor quarterly for beta emitters and iodine-131, and annually for tritium and strontium-90 at each entry point, beginning within 1 quarter after being notified by the Department. Monitoring shall be conducted as follows:

         (I)   Monitoring for gross beta particle activity shall be based on the average of an analysis of 3 monthly samples.

         (II)   For iodine-131, a composite of five consecutive daily samples shall be analyzed once each quarter. More frequent monitoring, as determined by the Department, shall be conducted when iodine-131 is identified in the finished water.

         (III)   Monitoring for strontium-90 and tritium shall be conducted by means of the analysis of 4 quarterly samples.

         (IV)   If the gross beta particle activity minus the naturally occurring potassium-40 beta particle activity at an entry point has a running annual average (computed quarterly) less than or equal to 15 pCi/L (screening level), the frequency of monitoring at that entry point shall be reduced to four consecutive quarterly samples taken once every 3 years. Systems shall collect all samples required in clause (B) during the reduced monitoring period.

         (V)   For systems in the vicinity of a nuclear facility, the system may utilize environmental surveillance data collected by the nuclear facility in lieu of monitoring at the system’s entry points, when the Department determines that the data is applicable to the system. If there is a release from a nuclear facility, systems that are using surveillance data shall begin monitoring at the system’s entry points in accordance with clause (B).

       (C)   Systems designated by the Department to monitor for beta particle and photon radioactivity may not apply to the State for a waiver from the monitoring frequencies specified in clause (A) or (B).

       (D)   Systems may analyze for naturally occurring potassium-40 beta particle activity from the same or equivalent sample used for the gross beta particle activity analysis. The potassium-40 beta particle activity shall be calculated by multiplying elemental potassium concentrations (in mg/L) by a factor of 0.82.

       (E)   If the gross beta particle activity minus the naturally occurring potassium-40 beta particle activity exceeds the screening level, an analysis of the sample shall be performed to identify the major radioactive constituents present in the sample. The results of the individual constituent analysis shall be reported in pCi/L, and the appropriate doses must be calculated and summed to determine compliance with the MCL, using the formula in 40 CFR 141.66(d)(2). Doses shall also be calculated and combined for measured levels of tritium and strontium to determine compliance.

       (F)   Systems shall monitor monthly at the entry points that exceed the MCL beginning the month after the exceedance occurs. Systems shall continue monthly monitoring until the system has established, by a rolling average of three monthly samples, that the MCL is being met. Systems that establish that the MCL is being met shall return to quarterly monitoring until they meet the requirements set forth in subclause (A)(I) or (B)(IV).

     (iii)   General monitoring and compliance requirements.

       (A)   The Department may require more frequent sampling than specified in subparagraphs (i) and (ii), or may require confirmation samples. The results of the initial and confirmation samples will be averaged for use in compliance determinations.

       (B)   Each system shall monitor at the time designated by the Department during each compliance period.

       (C)   Compliance with the MCLs will be determined based on the analytical results obtained at each entry point. If one entry point is in violation of an MCL, the system is in violation of the MCL.

         (I)   For systems monitoring more than once per year, compliance with the MCL is determined by a running annual average at each entry point. If the running annual average at an entry point is greater than the MCL, the system is in violation of the MCL. If a sample result will cause the running annual average to exceed the MCL at an entry point, the system is in violation of the MCL immediately.

         (II)   Systems shall include all samples taken and analyzed under this section in determining compliance, even if that number is greater than the minimum required.

         (III)   If a system does not collect all required samples when compliance is based on a running annual average of quarterly samples, compliance will be based on the running average of the samples collected.

         (IV)   If a sample result is less than the detection limit, zero will be used to calculate the annual average, unless a gross alpha particle activity is being used in lieu of radium-226 or uranium, or both. If the gross alpha particle activity result is less than detection, one-half of the detection limit will be used to calculate the annual average.

       (D)   The Department may delete results of obvious sampling or analytic errors.

Source

   The provisions of this §  109.301 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended March 24, 1989, effective March 25, 1989, 19 Pa.B. 1289; amended June 16, 1989, effective June 17, 1989, 19 Pa.B. 2543; corrected July 28, 1989, effective June 17, 1989, 19 Pa.B. 3164; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended October 7, 1994, effective October 8, 1994, 24 Pa.B. 5175; amended December 23, 1994, effective December 24, 1994, 24 Pa.B. 6404; corrected March 10, 1995, effective March 11, 1995, 25 Pa.B. 833; amended April 23, 1999, effective April 24, 1999, 29 Pa.B. 2231; amended July 20, 2001, effective July 21. 2001, 31 Pa.B. 3895 and 3938; amended August 9, 2002, effective August 10, 2002, 32 Pa.B. 3894; corrected December 5, 2003, effective August 10, 2002, 33 Pa.B. 5916; amended April 2, 2004, effective April 3, 2004, 34 Pa.B. 1762; amended June 18, 2004, effective June 19, 2004, 34 Pa.B. 3130; amended August 13, 2004, effective August 14, 2004, 34 Pa.B. 4435. Immediately preceding text appears at serial pages (304263), (304265) to (304267), (301755) to (301756), (290489) to (290500), (303177) to (303178), (290503) to (290508), (303179) to (303182) and (304269) to (304270).

Cross References

   This section cited in 25 Pa. Code §  109.202 (relating to State MCLs, MRDLs and treatment technique requirements); 25 Pa. Code §  109.302 (relating to special monitoring requirements); 25 Pa. Code §  109.303 (relating to sampling requirements); 25 Pa. Code §  109.305 (relating to fees); 25 Pa. Code §  109.408 (relating to tier 1 public notice—form, manner and frequency of notice); 25 Pa. Code §  109.503 (relating to public water system construction permits); 25 Pa. Code §  109.701 (relating to reporting and recordkeeping); 25 Pa. Code §  109.703 (relating to facilities operation); 25 Pa. Code §  109.705 (relating to sanitary survey); 25 Pa. Code §  109.710 (relating to disinfectant residual in the distribution system); 25 Pa. Code §  109.714 (relating to filter profile, filter self-assessment and comprehensive performance evaluations); 25 Pa. Code §  109.810 (relating to reporting and notification requirements); and 25 Pa. Code §  109.1003 (relating to monitoring requirements).