Subchapter G. SYSTEM MANAGEMENT RESPONSIBILITIES


Sec.


109.701.    Reporting and recordkeeping.
109.702.    Operation and maintenance plan.
109.703.    Facilities operation.
109.704.    Operator certification.
109.705.    Sanitary surveys.
109.706.    System distribution map.
109.707.    Emergency response plan.
109.708.    Planned service interruptions.
109.709.    Cross-connection control program.
109.710.    Disinfectant residual in the distribution system.
109.711.    Disinfection of facilities prior to placing them into service.
109.712.    Control of POE devices.
109.713.    Wellhead protection program.
109.714.    Filter profile, filter self-assessment and comprehensive performance evaluations.

Cross References

   This subchapter cited in 25 Pa. Code §  109.5 (relating to organization of chapter); 25 Pa. Code §  109.407 (relating to general public notification requirements); 25 Pa. Code §  109.409 (relating to Tier 2 public notice—form, manner and frequency of notice); and 25 Pa. Code §  109.505 (relating to requirements for noncommunity water systems).

§ 109.701. Reporting and recordkeeping.

 (a)  Reporting requirements for public water systems. Public water systems shall comply with the following requirements:

   (1)  General reporting requirements. Unless a different reporting period is specified in this chapter, the water supplier shall assure that the results of test measurements or analyses required by this chapter are reported to the Department within either the first 10 days following the month in which the result is received or the first 10 days following the end of the required monitoring period as stipulated by the Department, whichever is shorter. The test results shall include the following at a minimum:

     (i)   The name, address and public water system identification number (PWSID) of the public water system from which the sample was taken.

     (ii)   The name, address and identification number of the laboratory performing the analysis unless the analysis is not required to be performed by a certified laboratory.

     (iii)   The results of analytical methods, including negative results.

     (iv)   Contaminants.

     (v)   Analytical methods used.

     (vi)   The date of sample.

     (vii)   The date of analysis.

     (viii)   Sample location.

   (2)  Monthly reporting requirements for performance monitoring.

     (i)   The test results of performance monitoring required under §  109.301(1) (relating to general monitoring requirements) for public water suppliers providing filtration and disinfection of surface water or GUDI sources shall include the following at a minimum:

       (A)   For turbidity performance monitoring:

         (I)   The number of days of filtration operation.

         (II)   The number of filtered water turbidity measurements taken each month.

         (III)   The number of filtered water turbidity measurements that are less than or equal to .5 NTU for conventional, direct or other filtration technologies, or 1.0 NTU for slow sand or diatomaceous earth filtration technologies.

         (IV)   The date, time and values of any filtered water turbidity measurements exceeding 2.0 NTU.

         (V)   Instead of subclauses (III) and (IV), beginning January 1, 2002, for public water systems that serve 10,000 or more people and use conventional or direct filtration:

           (-a-)   The number of filtered water turbidity measurements that are less than or equal to 0.3 NTU.

           (-b-)   The date, time and values of any filtered water turbidity measurements exceeding 1 NTU.

         (VI)   Instead of clause (A)(III) and (IV), beginning January 1, 2005, for public water systems that serve fewer than 10,000 persons and use conventional or direct filtration:

           (-a-)   The number of filtered water turbidity measurements that are less than or equal to 0.3 NTU.

           (-b-)   The date, time and values of any filtered water turbidity measurements exceding 1 NTU.

         (VII)   Instead of subclauses (III) and (IV), beginning January 1, 2002, for public water systems that serve 10,000 or more people and use other filtration technologies:

           (-a-)   The number of filtered water turbidity measurements that are less than or equal to 0.3 NTU or a more stringent turbidity performance level requirement that is based upon onsite studies and is specified by the Department.

           (-b-)   The date, time and values of any filtered water turbidity measurements exceeding 1 NTU or a more stringent turbidity performance level requirement that is based upon onsite studies and is specified by the Department.

       (B)   For performance monitoring of the residual disinfectant concentration of the water being supplied to the distribution system:

         (I)   The date, time and lowest value each day.

         (II)   The date, duration and number of periods each day when the concentration is less than .2 mg/L for more than 4 hours.

       (C)   For performance monitoring of the residual disinfectant concentration at representative points in the distribution system report the following:

         (I)   The number of monthly routine samples required.

         (II)   The number of monthly routine samples collected and analyzed.

         (III)   The number of samples in which the residual disinfectant concentration was less than 0.02 mg/L.

         (IV)   For samples in which the residual disinfectant concentration was less than 0.02 mg/L: the date, time and value of each sample.

     (ii)   The test results of performance monitoring required under §  109.301(2) for public water suppliers using unfiltered surface water or GUDI sources shall include the following, at a minimum:

       (A)   For turbidity performance monitoring:

         (I)   The date, time and value of each sample that exceeds 1.0 NTU.

         (II)   The date, time and highest turbidity value, if the turbidity does not exceed 1.0 NTU in a sample.

       (B)   For performance monitoring of the residual disinfectant concentration of the water being supplied to the distribution system:

         (I)   The date, time and lowest value each day the concentration is less than the residual disinfectant concentration required under §  109.202(c)(1)(iii).

         (II)   If the concentration does not fall below that required under §  109.202(c)(1)(iii) during the month, report the date, time and lowest value measured that month.

       (C)   For performance monitoring of the residual disinfectant concentration at representative points in the distribution system, report the following:

         (I)   The number of monthly routine samples required.

         (II)   The number of monthly routine samples collected and analyzed.

         (III)   The number of samples in which the residual disinfectant concentration was less than 0.02 mg/L.

         (IV)   For samples in which the residual disinfectant concentration was less than 0.02 mg/L: the date, time and value of each sample.

       (D)   For performance monitoring of the fecal coliform or total coliform density determinations on samples of the source water immediately prior to disinfection: the date, time and value of each sample.

     (iii)   The test results from performance monitoring required under §  109.301(8)(v) of the residual disinfectant concentration of the water in the distribution system shall include the date, time and value of each sample.

     (iv)   The test results of heterotrophic plate count measurements taken under §  109.710(b) (relating to disinfectant residual in the distribution system) shall include the date, time and value of each sample.

   (3)  Compliance report. A public water supplier shall report the circumstances to the Department within 1 hour of discovery for the following violations or situations:

     (i)   A primary MCL or an MRDL has been exceeded or a treatment technique requirement has been violated under Subchapter B or K (relating to MCLs, MRDLs or treatment technique requirements; and lead and copper).

     (ii)   A sample result requires the collection of check samples under §  109.301.

     (iii)   Circumstances exist which may adversely affect the quality or quantity of drinking water including, but not limited to, the occurrence of a waterborne disease outbreak, a failure or significant interruption in key water treatment processes, a natural disaster that disrupts the water supply or distribution system, or a chemical spill or unexpected loading of possible pathogens into the source water that significantly increases the potential for drinking water contamination.

   (4)  Notice. The water supplier shall, within 10 days of completion of each public notification required under Subchapter D (relating to public notification) with the exception of a CCR, submit to the Department a certification that it has fully complied with the public notification requirements. The water supplier shall include with this certification a representative copy of each type of notice distributed, published, posted and made available to persons served by the system and to the media and a description of the means undertaken to make the notice available.

   (5)  Siting plan. The water supplier shall submit to the Department a written sample siting plan for routine coliform sampling as required by §  109.303(a)(2) (relating to sampling requirements) within 30 days of receipt of the Department’s request for this information.

     (i)   A sample siting plan shall include at a minimum the following:

       (A)   A list of available sample site locations in the distribution system to be used for routine monitoring purposes, including the first service connection (or Department approved equivalent) and dead ends.

       (B)   The name of the company or individual collecting the samples.

       (C)   A time period by which available sites representative of the distribution system are to be sampled during each monitoring period.

     (ii)   The Department’s approval of a sample siting plan will be based upon the following:

       (A)   The population served by the system.

       (B)   The accessibility of sample sites.

       (C)   The past monitoring history for the system.

       (D)   The completeness of the sample siting plan which includes the information specified in subparagraph (i) and other information relating to the criteria in this subparagraph necessary for evaluation of the sample siting plan.

     (iii)   A water supplier shall revise and resubmit its sample siting plan within 30 days of notification by the Department of a sample siting plan which fails to meet the criteria in subparagraphs (i) and (ii).

     (iv)   The water supplier shall notify the Department of subsequent revisions to an approved coliform sample siting plan for approval as they occur. Revisions to an approved coliform sample siting plan shall be submitted in written form to the Department within 30 days of notifying the Department of the revisions.

   (6)  Records. Upon request by the Department, the water supplier shall submit copies of records required to be maintained under this subchapter.

   (7)  Form. Reports required by this chapter shall be submitted in a manner or form acceptable to the Department.

   (8)  Reporting requirements for disinfectant residuals. Public water systems shall report MRDL monitoring data as follows:

     (i)   For systems monitoring for chlorine dioxide under §  109.301(13):

       (A)   The dates, results and locations of the samples that were taken during the previous month.

       (B)   Whether the MRDL was exceeded.

       (C)   Whether the MRDL was exceeded in any 2-consecutive daily samples and whether the resulting violation was acute or nonacute.

     (ii)   For systems monitoring for either chlorine or chloramines under §  109.301(13):

       (A)   The number of samples taken during each month of the previous quarter.

       (B)   The monthly arithmetic average of all samples taken in each month for the last 12 months.

       (C)   The arithmetic average of all monthly averages for the last 12 months.

       (D)   Whether the MRDL was exceeded.

   (9)  Reporting requirements for disinfection byproducts.

     (i)   Systems monitoring for TTHMs and HAA5 under §  109.301(12) shall report the following:

       (A)   Systems monitoring on a quarterly or more frequent basis shall report the following:

         (I)   The number of samples taken during the last quarter.

         (II)   The date, location and result of each sample taken during the last quarter.

         (III)   The arithmetic average of all samples taken in the last quarter.

         (IV)   The annual arithmetic average of the quarterly arithmetic averages for the last 4 quarters.

         (V)   Whether the annual arithmetic average exceeds the MCL for either TTHMs or HAA5.

       (B)   Systems monitoring less than quarterly but no less than annually shall report the following:

         (I)   The number of samples taken during the last year.

         (II)   The date, location and result of each sample taken during the last monitoring period.

         (III)   The arithmetic average of all samples taken in the last year.

         (IV)   Whether the annual arithmetic average exceeds the MCL for either TTHMs or HAA5.

       (C)   Systems monitoring less than annually shall report the following:

         (I)   The date, location and result of the last sample taken.

         (II)   Whether the sample exceeds the MCL for either TTHMs or HAA5.

     (ii)   Systems monitoring for chlorite under §  109.301(12) shall report the following:

       (A)   The number of samples taken during the last month.

       (B)   The date, location and result of each entry point and distribution sample taken during the last month.

       (C)   The arithmetic average of each three-sample set of distribution samples taken during the last month.

       (D)   Whether the monthly arithmetic average exceeds the MCL.

     (iii)   Systems monitoring for bromate under §  109.301(12) shall report the following:

       (A)   The number of samples taken during the last quarter.

       (B)   The date, location and result of each sample taken during the last quarter.

       (C)   The arithmetic average of the monthly arithmetic averages of all samples taken in the last year.

       (D)   Whether the annual arithmetic average exceeds the MCL.

   (10)  Reporting requirements for disinfection byproduct precursors. Systems monitoring for TOC under §  109.301(12) shall report in accordance with 40 CFR 141.134(d) (relating to reporting and recordkeeping requirements for disinfection byproduct precursors and enhanced coagulation or enhanced softening).

 (b)  Reporting requirements for community water systems. In addition to the reporting requirements for a public water system, a community water supplier shall comply with the following requirements:

   (1)  The water supplier shall prepare a monthly operational report on forms provided by the Department or in a form acceptable to the Department. The report shall be maintained on file by the operator for at least 2 years and submitted upon request of the Department. The report shall include at least the following:

     (i)   The water produced daily.

     (ii)   The chemical added daily.

     (iii)   The physical and chemical determinations taken daily.

     (iv)   Water-level monitoring data for supply and any associated monitoring wells.

     (v)   The maintenance performed.

     (vi)   Operational problems.

   (2)  The water supplier shall submit by March 31 an annual water supply report for the prior calendar year on forms provided by the Department or in a form acceptable to the Department. This report shall include information relating to water use, connections, distribution system and storage.

   (3)  The water supplier shall keep a record of complaints received from consumers related to the act or this chapter on forms provided by the Department or in a form acceptable to the Department. Water suppliers complying with the Pennsylvania Public Utility Commission (PUC) complaint recordkeeping requirements under 52 Pa. Code §  65.3 (relating to complaints) shall be in compliance with this subsection if the complaints related to the act or this chapter are cross referenced within the PUC required records in a manner to make them readily available. The records shall be maintained on file by the operator for at least 3 years and submitted upon request of the Department.

 (c)  Reporting requirements for nontransient noncommunity water systems. In addition to complying with the reporting requirements for public water systems under subsection (a), a nontransient noncommunity water system shall comply with subsection (b)(1) except that records of water produced daily are not required.

 (d)  Record maintenance. The public water supplier shall retain on the premises of the public water system or at a convenient location near the premises the following:

   (1)  Records of bacteriological analyses which shall be kept for at least 5 years, and records of chemical analyses which shall be kept for at least 12 years. Actual laboratory reports may be kept, or data may be transferred to tabular summaries, if the following information is included:

     (i)   The date, place and time of sampling, and the name of the person who collected the sample.

     (ii)   Identification of the sample as to whether it was a routine distribution system sample, check sample, raw or finished water sample or other special purpose sample.

     (iii)   The date of analysis.

     (iv)   The laboratory, certification number and person responsible for performing the analysis.

     (v)   The analytical technique and methods used.

     (vi)   The results of the analysis.

   (2)  Records of performance monitoring required under §  109.301 which shall be kept for at least 3 years. At a minimum, these records shall contain the reporting requirements under subsection (a).

   (3)  Records of action taken by the public water supplier to correct violations of MCLs, MRDLs or treatment technique requirements, which shall be kept for at least 3 years after the last action taken with respect to the particular violation involved.

   (4)  Copies of written reports or communications relating to sanitary surveys conducted by a water supplier or his agent, which shall be kept for at least 12 years.

   (5)  Records concerning a variance or exemption granted to the system which shall be kept at least 5 years following the expiration of the variance or exemption.

   (6)  Plans, specifications and permits for water system facilities which shall be kept for the life of the facility.

   (7)  Records concerning the use of acrylamide and epichlorohydrin shall be kept for at least 12 years. These records shall include verification that the chemicals used were certified for conformance with ANSI/NSF Standard 60 in accordance with §  109.606 (relating to chemicals, materials and equipment) and that the combination—or product—of dose and monomer level did not exceed the following:

     (i)   Acrylamide = 0.05% dosed at 1 ppm (or equivalent).

     (ii)   Epichlorohydrin = 0.01% dosed at 20 ppm (or equivalent).

   (8)  Copies of public notifications issued under Subchapter D and certifications made to the Department under subsection (a)(4) shall be kept for 3 years after issuance.

 (e)  Reporting requirements for public water systems required to perform individual filter monitoring under §  109.301(1)(iv).

   (1)  Public water systems required to perform individual filter monitoring shall report that they have conducted individual filter monitoring within 10 days following the end of each month that the system serves water to the public.

   (2)  Public water systems required to perform individual monitoring shall report individual filter turbidity results if individual filter turbidity measurements demonstrate that one or more of the following conditions exist:

     (i)   An individual filter has a measured turbidity level greater than 1.0 NTU in two consecutive measurements taken 15 minutes apart.

     (ii)   An individual filter has a measured turbidity level of greater than 0.5 NTU in two consecutive measurements taken 15 minutes apart at the end of the first 4 hours of continuous filter operation after the filter has been backwashed or otherwise taken offline.

     (iii)   An individual filter has a measured turbidity level greater than 1.0 NTU in two consecutive measurements taken 15 minutes apart at any time in each of 3-consecutive months.

     (iv)   An individual filter has a measured turbidity level greater than 2.0 NTU in two consecutive measurements taken 15 minutes apart at any time in each of 2-consecutive months.

   (3)  Individual filter turbidity monitoring reported as required under paragraph (2) shall include the following at a minimum:

     (i)   Filter number.

     (ii)   Turbidity measurements.

     (iii)   The dates on which the exceedance occurred.

     (iv)   If an individual filter demonstrates a condition under paragraph (2)(i) or (ii), the date on which a filter profile was produced or the date on which the reason for a turbidity exceedance was determined.

     (v)   If an individual filter demonstrates a condition under paragraph (2)(iii), the date on which a filter self-assessment was conducted.

     (vi)   If an individual filter demonstrates a condition under paragraph (2)(iv), the date on which a comprehensive performance evaluation was conducted.

 (f)  Alternative individual filter turbidity exceedance levels. Public water systems using lime softening may apply to the Department for alternative individual filter turbidity exceedance levels if they demonstrate that the higher individual filter turbidity levels are due to lime carryover and not to degraded filter performance.

 (g)  Monitoring plans for disinfectants, disinfection byproducts and disinfection byproduct precursors. Systems required to monitor for disinfection byproducts or disinfection byproduct precursors under §  109.301(12) or disinfectant residuals under §  109.301(13) shall develop and implement a monitoring plan. The system shall maintain the plan and make it available for inspection by the Department and the general public no later than 30 days following the applicable compliance dates. All systems that use either surface water or GUDI sources shall submit a copy of the monitoring plan to the Department no later than 30 days prior to the date of the first report required under this subchapter. The Department may also require the plan to be submitted by any other system, regardless of size or source water type. After review, the Department may require changes in any of the plan components.

   (1)  The plan shall include the following components:

     (i)   Specific locations and schedules for collecting samples for any parameters included in §  109.301(12) or (13).

     (ii)   How the system will calculate compliance with the MCLs, MRDLs and treatment techniques.

     (iii)   If approved for monitoring as a consecutive system, or if providing water to a consecutive system, the sampling plan shall reflect the entire distribution system.

     (iv)   Systems may consider multiple wells drawing water from a single aquifer as one treatment plant for determining the minimum number of TTHM and HAA5 samples required under §  109.301(12)(i).

   (2)  The system shall notify the Department of subsequent revisions to a monitoring plan as they occur. Revisions to a monitoring plan shall be submitted in written form to the Department within 30 days of notifying the Department of the revisions.

 (h)  Reporting and record maintenance requirements for systems recycling their waste streams.

   (1)  Public water systems using surface water or GUDI sources and providing conventional filtration or direct filtration treatment and that recycle spent filter backwash water, thickener supernatant, or liquids from dewatering processes shall notify the Department in writing by December 8, 2003. This notification shall include the following information:

     (i)   A plant schematic showing the origin of all flows that are recycled (including, but not limited to, spent filter backwash water, thickener supernatant and liquids from dewatering processes), the hydraulic conveyance used to transport them and the location where they are reintroduced back into the treatment plant.

     (ii)   Typical recycle flow in gallons per minute (gpm), the highest observed plant flow experienced in the previous year (gpm), design flow for the treatment plant (gpm) and Department-approved operating capacity for the plant.

   (2)  Record maintenance. Beginning June 8, 2004, public water systems using surface water or GUDI sources and providing conventional filtration or direct filtration and recycling spent filter backwash water, thickener supernatant, or liquids from dewatering processes shall collect and retain on file recycle flow information specified in this paragraph. This information is for the previous year of recycling and shall be available to the Department for review and evaluation at the Department’s request:

     (i)   A copy of the recycle notification and information submitted to the Department under subsection (h).

     (ii)   A list of all recycle flows and the frequency with which they are returned.

     (iii)   Average and maximum backwash flow rate through the filters and the average and maximum duration of the filter backwash process in minutes.

     (iv)   Typical filter run length and a written summary of how filter run length is determined.

     (v)   The type of treatment provided for the recycle flow.

     (vi)   Data on the physical dimensions of the equalization or treatment units, or both, typical and maximum hydraulic loading rates, type of treatment chemicals used and average dose and frequency of use, and frequency at which solids are removed, if applicable.

Source

   The provisions of this §  109.701 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended June 16, 1989, effective June 17, 1989, 19 Pa.B. 2543; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended October 7, 1994, effective October 8, 1994, 24 Pa.B. 5175; amended December 23, 1994, effective December 24, 1994, 24 Pa.B. 6404; amended April 23, 1999, effective April 24, 1999, 29 Pa.B. 2231; amended July 20, 2001, effective July 21, 2001, 31 Pa.B. 3895 and 3938; amended August 9, 2002, effective August 10, 2002, 32 Pa.B. 3894; amended April 2, 2004, effective April 3, 2004, 34 Pa.B. 1758; amended June 18, 2004, effective June 19, 2004, 34 Pa.B. 3130; amended August 13, 2004, effective August 14, 2004, 34 Pa.B. 4435. Immediately preceding text appears at serial pages (304279) to (304281), (290555) to (2905660) and (304283).

Cross References

   This section cited in 25 Pa. Code §  109.202 (relating to State MCLs, MRDLs and treatment technique requirements); 25 Pa. Code §  109.301 (relating to general monitoring requirements); 25 Pa. Code §  109.303 (relating to sampling requirements); 25 Pa. Code §  109.407 (relating to general public notification requirements); 25 Pa. Code §  109.408 (relating to tier 1 public notice—form, manner and frequency of notice); 25 Pa. Code §  109.409 (relating to tier 2 public notice—form, manner and frequency of notice); 25 Pa. Code §  109.707 (relating to emergency response plan); 25 Pa. Code §  109.714 (relating to filter profile, filter self-assessment and comprehensive performance evaluations); 25 Pa. Code §  109.1008 (relating to system management responsibilities); and 25 Pa. Code §  109.1107 (relating to system management responsibilities).

§ 109.702. Operation and maintenance plan.

 (a)  A community water supplier shall develop an operation and maintenance plan for the community water system. The operation and maintenance plan shall conform to the guidelines contained in the Department’s Public Water Supply Manual and shall contain at least the following information:

   (1)  A description of the facilities.

   (2)  An explanation of startup and normal operation procedures.

   (3)  A routine maintenance program.

   (4)  Records and reporting system.

   (5)  Sampling and analyses program.

   (6)  A public notification program including appropriate advance preparations, such as public notice templates, an explanation of appropriate methods of delivery and a designation of public notice recipients for each tier type.

   (7)  Staffing and training.

   (8)  Sanitary survey program including the wellhead protection program for any water system that develops one under §  109.713 (relating to wellhead protection programs).

   (9)  Safety program.

   (10)  Emergency plan and operating procedures.

   (11)  Manufacturer’s manuals.

   (12)  An interconnect, valve and blowoff exercise and testing program.

 (b)  The community water supplier shall implement the operation and maintenance plan in accordance with accepted practices of the water supply industry.

 (c)  The operation and maintenance plan shall be reviewed and updated as necessary to reflect changes in the operation or maintenance of the water system. The plan shall be bound and placed in locations which are readily accessible to the water system’s personnel, and shall be presented upon request to the Department.

 (d)  Noncommunity water suppliers may be directed by the Department to develop and implement an operation and maintenance plan as provided for in this section when the public health is threatened by inadequate operation and maintenance of the facilities.

Source

   The provisions of this §  109.702 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended October 7, 1994, effective October 8, 1994, 24 Pa.B. 5175; amended August 9, 2002, effective August 10, 2002, 32 Pa.B. 3894. Immediately preceding text appears at serial pages (281913) to (281914).

Cross References

   This section cited in 25 Pa. Code §  109.503 (relating to public water system construction permits); and 25 Pa. Code §  109.1107 (relating to system management responsibilities).

§ 109.703. Facilities operation.

 (a)  Public water system facilities approved by written permit from the Department shall be operated in a manner consistent with the terms and conditions of the permit to achieve the level of treatment for which the facilities were designed.

 (b)  For surface water or GUDI sources, a public water supplier using filtration shall comply with the following requirements:

   (1)  By July 1, 1990, suppliers using conventional or direct filtration shall, after filter backwash, and before putting the backwashed filter back on line, filter-to-waste until one of the following occurs:

     (i)   The filter bed effluent turbidity is less than .5 NTU at the normal production flow rate.

     (ii)   When source water turbidity is less than 1.0 NTU, a 50% reduction in turbidity is achieved.

   (2)  Beginning May 16, 1992, a supplier using slow sand filtration shall, following sanding, scraping or resanding of slow sand filters, filter-to-waste until one of the following occurs:

     (i)   The filter bed effluent turbidity is less than 1.0 NTU at the normal production flow rate.

     (ii)   A reduction in turbidity is achieved when the source water turbidity is less than 1.0 NTU.

   (3)  Beginning May 16, 1992, a supplier using diatomaceous earth filtration shall, following backwashing and recoating of diatomaceous earth filters, filter-to-waste until one of the following occurs:

     (i)   The filter bed effluent turbidity is less than 1.0 NTU at the normal production flow rate.

     (ii)   A reduction in turbidity is achieved when the source water turbidity is less than 1.0 NTU.

   (4)  For a conventional or direct filtration facility permitted prior to March 25, 1989, without filter-to-waste capability, the Department, upon the supplier’s request, may allow the supplier to utilize other operating techniques which minimize the initial increased turbidity peak when a filter is initially placed back into service after backwashing. The technique, which may include filter settling periods, ramping open the effluent valve or use of a coagulant in the backwash water, shall be justified by a filter performance study approved by the Department.

   (5)  Except for public water systems covered under §  109.301(1)(iv) (relating to general monitoring requirements), a system with conventional or direct filtration facilities permitted prior to March 25, 1989, without individual filter bed turbidity monitoring capabilities shall conduct an annual filter bed evaluation program, acceptable to the Department, which includes an evaluation of filter media, valves, surface sweep and sampling of filter turbidities over one entire filter run; and shall submit to the Department, with the Annual Water Supply Report, a study that demonstrates that the water supplier’s filter-to-waste or alternate approved operating procedures are meeting the operating conditions under paragraph (1) or (4).

Source

   The provisions of this §  109.703 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended March 24, 1989, effective March 25, 1989, 19 Pa.B. 1289; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended July 20, 2001, effective July 21, 2001, 31 Pa.B. 3895. Immediately preceding text appears at serial pages (254822) to (254823).

§ 109.704. Operator certification.

 (a)  Community water systems shall have personnel certified under the Sewage Treatment Plant and Waterworks Operators’ Certification Act (63 P. S. § §  1001—1015) and qualified by experience and education to operate and maintain a public water system.

 (b)  Noncommunity water systems shall have competent personnel qualified to operate and maintain the system’s facilities.

 (c)  Beginning July 21, 2004, nontransient noncommunity water systems that provide water that contains a chemical disinfectant shall be operated by qualified personnel certified under the Sewage Treatment Plant and Waterworks Operators’ Certification Act (63 P. S. § §  1001—1015). The minimum certification to oper-ate these facilities shall be a certificate to operate plants with disinfection only, under §  303.2 (relating to waterworks operators certificates).

Source

   The provisions of this §  109.704 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended July 20, 2001, effective July 21, 2001, 31 Pa.B. 3895. Immediately preceding text appears at serial pages (254823) to (254824).

Cross References

   This section cited in 25 Pa. Code §  109.304 (relating to analytical requirements); 25 Pa. Code §  109.504 (relating to public water system operation permits); and 25 Pa. Code §  252.6 (relating to accreditation-by-rule).

§ 109.705. Sanitary surveys.

 (a)  A community water supplier shall conduct a sanitary survey of the water system at least annually. The survey shall include the following activities:

   (1)  Watershed surveillance consisting of an inspection of portions of the drainage area or wellhead protection area necessary to identify and evaluate actual and probable sources of contamination. An inspection of a wellhead protection area shall include a review of available information pertaining to possible sources of contamination such as underground storage tanks, onlot disposal systems and other activities that may have an adverse impact on water quality or quantity. Specific hydrogeological studies of sources of contamination are not necessary unless required under §  109.4, §  109.602 or §  109.603 (relating to general requirements; acceptable design; and source quality and quantity) or other rules of the Department.

   (2)  Evaluation of source protection, intake structures and transmission facilities.

   (3)  Treatment facilities inspection consisting of an evaluation of the effectiveness of the operation and maintenance procedures and the condition and operability of permitted facilities.

   (4)  Evaluation of finished water storage facilities and the distribution system.

   (5)  Pressure surveys consisting of a measurement of pressures at representative points in the distribution system, which shall include new water line extensions. Surveys shall be made during periods of maximum and minimum usage. Records of these surveys shall show the date and time of the beginning and end of the test and the location at which the test was made.

 (b)  A community water system which does not collect five or more routine coliform samples per month shall do one of the following:

   (1)  Undergo a sanitary survey conducted by the Department by June 29, 1994, and thereafter undergo a subsequent sanitary survey conducted by the Department at a minimum of every 3 years after the initial sanitary survey, depending on the type of source, treatment and population served.

   (2)  Increase the number of routine coliform samples collected to at least five samples per month if the Department does not conduct a sanitary survey by June 29, 1994, or within 3 years following the initial or a subsequent sanitary survey. This increased sampling frequency shall be in place of the monitoring frequency requirements for coliforms in §  109.301(3)(i) (relating to general monitoring requirements) and shall remain in effect through the month in which the next sanitary survey is conducted by the Department.

 (c)  A noncommunity water system which does not collect five or more routine coliform samples per month shall do one of the following:

   (1)  Undergo an initial sanitary survey conducted by the Department by June 29, 1999, and thereafter undergo a subsequent sanitary survey at a minimum of every 5 years after the initial sanitary survey, except that noncommunity systems using only protected and disinfected groundwater shall undergo subsequent sanitary surveys at a minimum of every 10 years after the initial sanitary survey.

   (2)  Increase the number of routine coliform samples collected to at least five samples per month if the Department does not conduct a sanitary survey by June 29, 1999, or within 5 or 10 years using the criteria in paragraph (1), following the initial or a subsequent sanitary survey. This increased sampling frequency shall be in place of the monitoring frequency requirements for coliforms in §  109.301(3)(i) and shall remain in effect through the month in which the next sanitary survey is conducted by the Department.

Source

   The provisions of this §  109.705 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended May 15, 1992, effective May 16, 1992, Pa.B. 2621; amended October 7, 1994, effective October 8, 1994, 24 Pa.B. 5175. Immediately preceding text appears at serial pages (170202) to (170204).

Cross References

   This section cited in 25 Pa. Code §  109.301 (relating to general monitoring requirements).

§ 109.706. System distribution map.

 (a)  The community water supplier shall prepare and maintain on file a detailed map of the water system’s transmission and distribution facilities.

 (b)  A noncommunity water supplier shall submit a detailed map of the water system’s transmission and distribution facilities at the request of the Department.

 (c)  The map shall include information sufficient to allow the Department to analyze the distribution system and determine quantity, pressure and direction of flow from the sources to the customers, and shall include the type and size of pipes within the distribution system. The map shall be updated at least annually.

Source

   The provisions of this §  109.706 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended December 23, 1994, effective December 24, 1994, 24 Pa.B. 6404. Immediately preceding text appears at serial page (192119).

§ 109.707. Emergency response plan.

 (a)  A community water supplier shall develop a plan for the provision of safe and adequate drinking water under emergency circumstances, and submit the plan to the Department for approval by December 8, 1985. The emergency response plan shall conform to the guidelines contained in the Department’s Public Water Supply Manual and shall contain at least the following information:

   (1)  Identification of probable emergency situations, including, but not limited to, those specified in §  109.701(a)(3)(iii) (relating to reporting and recordkeeping), and alternative solutions to respond to situations including how the system will maintain its ability to provide service in the event of contamination or an outage of one or more of its sources of supply. Consideration shall be given to providing reserve capacity according to §  109.609 (relating to reserve capacity and finished water storage).

   (2)  Procedures for communications and coordination with the local emergency management organization.

 (b)  The plan shall be kept on file in a readily accessible location by the public water supplier.

 (c)  The plan shall be reviewed and updated at least annually.

Source

   The provisions of this §  109.707 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended December 23, 1994, effective December 24, 1994, 24 Pa.B. 6404; amended August 9, 2002, effective August 10, 2002, 32 Pa.B. 3894. Immediately preceding text appears at serial page (281918).

Cross References

   This section cited in 25 Pa. Code §  109.407 (relating to general public notification requirements).

§ 109.708. Planned service interruptions.

 The public water supplier shall give reasonable notice to the affected customers prior to a planned service interruption affecting quantity or quality of the water delivered to the customer. If the interruption is scheduled to exceed 8 hours and affect 15 or more service connections the water supplier shall also notify the Department.

Source

   The provisions of this §  109.708 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479.

§ 109.709. Cross-connection control program.

 (a)  No person may introduce contaminants into a public water supply through a service connection of a public water system.

   (1)  It shall be the responsibility of the customer to eliminate cross-connections or provide backflow devices to prevent contamination of the distribution system from both backsiphonage and backpressure. Individual backflow preventors shall be acceptable to the public water supplier.

   (2)  If the customer fails to comply with paragraph (1) within a reasonable period of time, the water supplier shall discontinue service after reasonable notice has been made to the customer.

 (b)  At the direction of the Department, the public water supplier shall develop and implement a comprehensive control program for the elimination of existing cross-connections or the effective containment of sources of contaminations, and prevention of future cross-connections. A description of the program, including the following information, shall be submitted to the Department for approval:

   (1)  A description of the methods and procedures to be used.

   (2)  An implementation schedule for the program.

   (3)  Legal authority for implementation of the program, such as, by ordinance or rules.

   (4)  A time schedule for inspection of nonresidential customers’ premises for cross-connections with appropriate recordkeeping.

   (5)  A public education program for residential customers.

   (6)  A description of the methods and devices which will be used to protect the water system.

   (7)  A program for the review of plans for new users to assure that no new cross-connections are developed.

   (8)  Provisions for discontinuance of water service, after reasonable notice, to premises where cross-connections exist.

Source

   The provisions of this §  109.709 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479.

§ 109.710. Disinfectant residual in the distribution system.

 (a)  A disinfectant residual acceptable to the Department shall be maintained throughout the distribution system of the community water system sufficient to assure compliance with the microbiological MCLs and the treatment technique requirements specified in §  109.202 (relating to State MCLs, MRDLs and treatment technique requirements). The Department will determine the acceptable residual of the disinfectant considering factors such as type and form of disinfectant, temperature and pH of the water, and other characteristics of the water system.

 (b)  A public water system that uses surface water or GUDI sources or obtains finished water from another permitted public water system using surface water or GUDI sources shall comply with the following requirements:

   (1)  As a minimum, a detectable residual disinfectant concentration of 0.02 mg/L measured as total chlorine, combined chlorine or chlorine dioxide shall be maintained throughout the distribution system as demonstrated by monitoring conducted under §  109.301(1) and (2) or (8)(v) (relating to general monitoring requirements).

   (2)  Sampling points with nondetectable disinfectant residuals which have heterotrophic plate count (HPC) measurements of less than 500/ml are deemed to be in compliance with paragraph (1).

   (3)  When the requirements of paragraph (1) or (2) cannot be achieved, the supplier shall initiate an investigation under the Department’s direction to determine the cause, potential health risks and appropriate remedial measures.

 (c)  Public water systems may increase residual chlorine or chloramine, but not chlorine dioxide, disinfectant levels in the distribution system to a level that exceeds the MRDL for that disinfectant and for a time necessary to protect public health or to address specific microbiological contamination problems caused by circumstances such as, but not limited to, distribution line breaks, storm runoff events, source water contamination events or cross-connection events.

Source

   The provisions of this §  109.710 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; corrected December 14, 1984, effective December 8, 1984, 14 Pa.B. 4511; amended March 24, 1989, effective March 25, 1989, 19 Pa.B. 1289; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended July 20, 2001, effective July 21, 2001, 31 Pa.B. 3895 and 3938; amended August 13, 2004, effective August 14, 2004, 34 Pa.B. 4435. Immediately preceding text appears at serial page (290569).

Cross References

   This section cited in 25 Pa. Code §  109.701 (relating to reporting and record keeping).

§ 109.711. Disinfection of facilities prior to placing them into service.

 (a)  After construction or modification of a facility and before the facility is placed in service, it shall be properly disinfected. The facility may not be placed in service until the public water supplier demonstrates to the satisfaction of the Department that the facility has been adequately disinfected.

 (b)  After repairing a facility or performing other activities which place the facility out of service, and before returning the facility to service, the public water supplier shall disinfect the facilities in accordance with the most recent procedures established by the American Water Works Association.

Source

   The provisions of this §  109.711 adopted December 7, 1984, effective December 8, 1984, 14 Pa.B. 4479; amended May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621. Immediately preceding text appears at serial page (139104).

§ 109.712. Control of POE devices.

 (a)  The public water supplier shall be responsible for control of POE devices installed under a permit according to §  109.503(a)(2) (relating to public water system construction permits). This includes the installation, operation and routine maintenance of each device.

 (b)  A public water supplier which installs a POE device shall obtain and maintain a right-of-access to the house, building or other facility where the POE device is installed in the form of a covenant running with the land.

Source

   The provisions of this §  109.712 adopted May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621.

§ 109.713. Wellhead protection program.

 For water suppliers seeking to obtain Department approval for a wellhead protection program, the wellhead protection program shall consist of the following:

   (1)  A steering committee composed of the necessary representatives, including, but not limited to, the water supplier, local government officials from the affected jurisdictions and potentially affected industry, to designate responsibilities for the planning and implementation of wellhead protection activities.

   (2)  Public participation and education activities to promote awareness and encourage local support of wellhead protection activities.

   (3)  Zone II and Zone III wellhead protection area delineation performed in accordance with methodology provided by the Department. Methods applicable to that hydrogeologic setting shall be utilized and site-specific hydraulic and hydrogeologic information shall include, but is not limited to, pumping rate or yield, aquifer properties, water table or potentiometric surface configuration and hydrogeologic mapping.

   (4)  Identification of existing and potential sources of contamination within each wellhead protection area.

   (5)  Development and implementation of wellhead protection area management approaches to protect the water supply source from activities that may contaminate the source. These approaches may include, but are not limited to, one or more of the following actions:

     (i)   Purchase of the wellhead protection area by the water system.

     (ii)   Adoption of municipal ordinances or regulations controlling, limiting or prohibiting future potential sources of contamination within the wellhead protection area.

     (iii)   Adoption of municipal ordinances or regulations establishing design and performance standards for potential sources of contamination within the wellhead protection area.

     (iv)   Transfer of development rights within the wellhead protection area to land outside of the wellhead protection area.

     (v)   A groundwater monitoring network that serves as an early warning system.

     (vi)   Public education programs.

     (vii)   Other methods approved by the Department which will ensure an adequate degree of protection for the source.

   (6)  Contingency planning for the provision of alternate water supplies in the event of contamination of a well, spring or infiltration gallery and emergency responses to incidents that may impact water supply source quality.

   (7)  New water supply source siting provisions to ensure the protection of new wells, springs or infiltration galleries.

Source

   The provisions of this §  109.713 adopted October 7, 1994, effective October 8, 1994, 24 Pa.B. 5175.

Cross References

   This section cited in 25 Pa. Code §  109.702 (relating to operation and maintenance plan).

§ 109.714. Filter profile, filter self-assessment and comprehensive performance evaluations.

 Public water systems are required to perform or conduct a filter profile, filter self-assessment or CPE if any individual filter monitoring conducted under §  109.301(1)(iv) (relating to general monitoring requirements) demonstrates one or more of the conditions in paragraphs (1)—(3).

   (1)  If an individual filter demonstrates a condition under §  109.701(e)(2)(i) or (ii) (relating to reporting and recordkeeping), the public water system shall notify the Department within 24 hours of the individual filter turbidity level exceedance and shall report the obvious reason for the abnormal filter performance. If a system serving 10,000 or more persons is not able to identify the reason for the exceedance, the system shall produce a filter profile within 7 days of the exceedance and report to the Department that a filter profile was produced.

   (2)  If an individual filter demonstrates a condition under §  109.701(e)(2)(iii), the public water system shall notify the Department within 24 hours of the individual filter turbidity level exceedance, shall conduct a self-assessment of the filter within 14 days of the exceedance and shall report to the Department that a filter self-assessment was conducted. A filter self-assessment shall consist of at least the following components:

     (i)   Assessment of filter performance.

     (ii)   Development of a filter profile.

     (iii)   Identification and prioritization of factors limiting filter performance.

     (iv)   Assessment of the applicability of corrections.

     (v)   Preparation of a filter self-assessment report.

     (vi)   For public water suppliers serving fewer than 10,000 persons, if a self-assessment is required, the public water supplier shall report the date that it was triggered and the date that it was completed.

   (3)  If an individual filter demonstrates a condition under §  109.701(e)(2)(iv),the public water system shall:

     (i)   Notify the Department within 24 hours of the turbidity level exceedance.

     (ii)   Arrange for the conduction of a CPE by the Department no later than 30 days following the turbidity level exceedance.

     (iii)   Ensure that the CPE is completed and submitted to the Department no later than 90 days following the turbidity level exceedance.

     (iv)   Instead of subparagraphs (ii) and (iii), for public water systems serving fewer than 10,000 persons:

       (A)   Arrange for the conduction of a CPE by the Department no later than 60 days following the turbidity level exceedance.

       (B)   Ensure that the CPE is completed and submitted to the Department no later than 120 days following the turbidity level exceedance.

       (C)   A new CPE is not required if a CPE was completed by the Department within the previous 12 months, or the system and the Department are jointly participating in a program involving a combination of CPE results as the bases for implementing process control priority-setting techniques and maintaining long-term involvement to systematically train staff and administrators at the system.

       (D)   If a CPE is required, the public water system shall report that a CPE is required and the date that it was triggered.

Source

   The provisions of this §  109.714 adopted July 20, 2001, effective July 21, 2001, 31 Pa.B. 3938; amended June 18, 2004, effective June 19, 2004, 34 Pa.B. 3130. Immediately preceeding text appears at serial pages (290571) to (290572).



No part of the information on this site may be reproduced for profit or sold for profit.

This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.