§ 284.418. Storage and containment of ash residue from infectious or chemotherapeutic waste incineration.

 (a)  Ash residue from infectious or chemotherapeutic waste incineration shall be stored in accordance with the following:

   (1)  In an enclosed container, which may include a properly tarped container, or in an enclosed area, which may include an adequately ventilated building.

   (2)  On a pad that is no more permeable than 1 x 10-7 cm./sec.

   (3)  To prevent the release, dispersal or discharge of ash residue into the air, water or onto land.

 (b)  Ash residue may be commingled with other municipal waste if the commingled waste is from one generator and if storage of the commingled waste is in accordance with subsection (a).

Cross References

   This section cited in 25 Pa. Code §  284.321 (relating to infectious waste monitoring requirements).



No part of the information on this site may be reproduced for profit or sold for profit.

This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.