GENERAL REQUIREMENTS
§ 13.11. Suitability.
(a) Tanks, cylinders, equipment and appliances utilized in the storage, handling, and use of liquefied petroleum gas shall be of a type and construction suitable for such purpose.
(b) Shutoff valves and equipment, liquid or gas which may be subjected to container pressure shall be suitable for liquefied petroleum gas service and be designed for not less than 250 pounds per square inch.
(c) No connectors or fittings shall be utilized throughout liquefied petroleum gas systems unless suitable for the particular purpose used. The design and material used in all connectors and fittings shall provide strength sufficient to prevent failure within the maximum pressure to which they may be subjected in normal operation.
Cross References This section cited in 34 Pa. Code § 13.4 (relating to scope); and 34 Pa. Code § 13.96 (relating to filling of cylinders).