§ 13.32. Location.

 (a)  Tanks shall be located with respect to the nearest building or line of adjoining property which may be built upon according to the following table:


Minimum Distances
Between
Water capacityContainersaboveground
per containerundergroundabovegroundcontainers
(in gallons)(in feet)(in feet)
Less than 12510NoneNone
125—50010103
501—2,00025253
Over 2,00050503

 (b)  The distance requirements described in subsection (a) may be reduced to not less than ten feet for a single container of 1,200 or less gallons water capacity if the container is at least 25 feet from another LP-Gas container of more than 125 gallons water capacity.

Cross References

   This section cited in 34 Pa. Code §  3.12 (relating to frequency of inspection); 34 Pa. Code §  13.4 (relating to scope); and 34 Pa. Code §  13.33 (relating to bulk storage).



No part of the information on this site may be reproduced for profit or sold for profit.

This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.