BULK FILLING PLANTS, INDUSTRIAL ESTABLISHMENTS,
AND UTILITIES
§ 13.71. Location.
(a) The cylinder filling rooms shall be located far from storage tanks and such distance shall never be less than 10 feet from them.
(b) Tank truck filling station outlets shall be located far from pumps and compressors and in such distance shall not be less than 10 feet from them.
(c) If pumps and compressors are housed in one or more separate buildings they shall also be located far from storage tanks and all sources of ignition. However, in no case shall this distance be less than 10 feet from tanks and 25 feet from sources of ignition.
(d) No boiler or any source of ignition shall be located in a building used for filling purposes except when permitted by the Department.