CHAPTER 27. LIGHTING
GENERAL PROVISIONS Sec.
27.1. Definitions.
27.2. Scope.
27.3. Penalty.
SPECIFICATIONS FOR ALL INSTALLATIONS
27.11. General.
27.12. Glare.
27.13. Distribution of light.
27.14. Emergency lighting.
27.15. Intensity of illumination.
27.16. Dust and gas.Authority The provisions of this Chapter 27 issued under act of June 2, 1913 (P. L. 396, No. 267) (71 P. S. § § 14411451); and section 15 of the act of May 18, 1937 (P. L. 654, No. 174) (43 P. S. § 25-15), unless otherwise noted.
Source The provisions of this Chapter 27 adopted May 10, 1923, amended through August 1, 1968, unless otherwise noted.
Cross References This chapter cited in 34 Pa. Code § 13.73 (relating to lighting); 34 Pa. Code § 29.127 (relating to location); 34 Pa. Code § 39.22 (relating to yard and internal housekeeping); 34 Pa. Code § 41.32 (relating to construction); 34 Pa. Code § 45.11 (relating to mechanical power transmission and machine layout); 34 Pa. Code § 47.64 (relating to general requirements); 34 Pa. Code § 47.164 (relating to lighting and heating); and 34 Pa. Code § 47.193 (relating to workrooms).
GENERAL PROVISIONS
§ 27.1. Definitions.
The following words and terms, when used in this chapter, have the following meanings, unless the context clearly indicates otherwise:
Foot-candleThe lighting effect produced upon an object by a standard candle at a distance of 1 foot.
MinimizeTo reduce to the smallest practical proportion.
Nonflammable materialMaterial which will not readily burn or ignite.§ 27.2. Scope.
This chapter sets forth rules to safeguard the lives, limbs and health of workers in industries in which industrial lighting is necessary, and places the responsibility of complying with the provisions of this chapter upon both employer and employe.
§ 27.3. Penalty.
Any person who violates any of the provisions of this chapter or any regulations of the Department or who interferes with the Department or its authorized representative in the enforcement of the provisions or regulations shall be penalized under section 15 of act of May 18, 1937 (P. L. 654, No. 174) (43 P. S. § 25-15).
§ 27.11. General.
(a) Places requiring light. Working or traversed spaces in buildings or grounds and all working places in establishments or on their premises during the time of use, shall be supplied with light in accordance with this chapter.
(b) Measurements. The location at which the principal illumination is required is expressed in this chapter as at the work. Measurement of the illumination shall be made at this location in the usual plane in which the work is done; that is, on the horizontal, vertical or intermediate plane, as the case may be.
(c) Method of measurement. For the purpose of light measurements, a standardized photometer shall be used and the measurements shall be made at such locations specified in Tables I and II of this chapter.
(d) Maintenance. Equipment for both natural and artificial lighting shall be maintained in a clean and safe condition at all times.
§ 27.12. Glare.
(a) Diffusing accessories. Lamps producing glare in the ordinary field of vision from any position at which work is performed, or such lamps located in traversed spaces in buildings, shall be provided with shades, reflectors, diffusing glassware or other accessories, installed and arranged in such manner as to minimize glare. The devices shall be made of substantial construction and made of nonflammable material.
(b) Exceptions. The requirements of subsection (a) do not apply to lamps used for a temporary decorative purpose if an unusual or harmful glare is not created.
The provisions of this § 27.13 amended January 27, 1978, 8 Pa.B. 252. Immediately preceding text appears at serial page (8447).
§ 27.14. Emergency lighting.
Emergency lighting systems shall be required in establishments as required by Section 1 of the Special Regulations for Emergency Lighting Systems used when loss of power may cause illumination less than the minimum required by the applicable provisions of this chapter.
§ 27.15. Intensity of illumination.
The following table shall be used in determining the illumination levels for various office tasks and locations, the column at right indicating acceptable range of footcandles required:
TABLE I
Description Acceptable Range of
Footcandles on the
Task1. General Offices General Office Work 56-70 Accounting, Bookkeeping 120-150 Drafting & Designing 120-150 Private Offices 56-70 2. Conference Rooms 1/2-70* 3. Corridors, Elevators, Escalators, Stairways 16-20 4. Lobbies, Reception Areas 10-30 5. Washrooms 24-30
*More than one lighting system and/or dimming area desirable
Not less than 1/5 the level of nearby offices
May be more when planned for transition with daylight or other areas
Source The provisions of this § 27.15 amended January 27, 1978, 8 Pa.B. 252. Immediately preceding text appears at serial pages (8448) to (8458).
§ 27.16. Dust and gas.
Gas, vapor and dust-proof lighting fixtures shall be provided at all places where explosive gas, vapor or dust accumulates.