34 Pa. Code § 3a.35. Ladders and runways.

§ 3a.35. Ladders and runways.

 (a)  Walkways, runways and platforms are required between and on top of boilers, which are more than 8-feet high from the operating floor to afford accessibility for the operation and servicing.

 (b)  Walkways, runways and platforms must meet the following requirements:

   (1)  Be constructed of metal.

   (2)  Be constructed of safety treads, standard grating, or similar material with a minimum clear width of 30 inches.

   (3)  Be constructed by bolts, welds or rivets.

   (4)  Be equipped with handrails that are 42-inches high with an intermediate rail and 6-inch toeboard.

 (c)  A stairway that is a means of access to the walkways, runways or platforms must not exceed an angle of 45°.

 (d)  A ladder that serves as a means of access to walkways, runways or platforms must be constructed:

   (1)  Of metal.

   (2)  So the rungs extend through the side members and are permanently secured to the side rails.

   (3)  So the front of the rungs have a distance of at least 30 inches from the nearest permanent object on the climbing side of the ladder.

   (4)  So the back of the rungs have a distance of at least 6 1/2 inches from the nearest permanent object.

   (5)  So there is a clear width of at least 15 inches from the centerline of the ladder on either side across the front of the ladder.

 (e)  A welder qualified under Standard Qualification Procedures of the American Welding Society is required for welding a walkway, runway, platform or ladder.

 (f)  A walkway, runway or platform exceeding 6 feet in length must have at least two means of exit access.



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.