![]()
CHAPTER 50. GENERAL REQUIREMENTSBUILDINGS
OCCUPANCY GROUP Sec.
50.1. Occupancy groups.
50.2. Occupancy separations and mixed occupancies.
50.3. Prohibited occupancy mixtures.
CONSTRUCTION TYPES
50.11. Construction tables.
MEANS OF EGRESS
50.21. Definitions.
50.22. Exit accessibility standards.
50.23. Means of egress capacity.
50.24. Exit doors and exit access doors.
50.25. Stair towers.
50.26. Intercommunicating stairway.
50.27. Ramps.
50.28. Horizontal exits.
50.29. Escalators.
VERTICAL OPENINGS
50.31. Vertical openings 9 square feet or more.
50.32. Vertical openings less than 9 square feet.
50.33. Fire door assemblies.
50.34. Exterior openings.
INTERIOR FINISH
50.41. Definitions.
50.42. Basic material used.
50.43. Classification.
MANUAL AND AUTOMATIC FIRE ALARM SYSTEMS
50.51. Manual system.
50.52. Automatic system.
50.53. General fire alarm requirements.
50.55. Maintenance.
50.56. Testing new equipment.
50.57. Fire drills.
50.58. Inspection and maintenance of detection devices in apartments.
EMERGENCY LIGHTING SYSTEMS
50.61. General requirements.
50.62. Storage battery systems.
50.63. Unit systems.
50.64. Internal combustion engine generator systems.
EXTINGUISHERS AND SPRINKLER SYSTEMS
50.71. Fire extinguishers.
50.72. Automatic sprinkler systems.
RESTROOM EQUITY
50.81. Purpose.
50.82. Jurisdiction and effective dates.
50.83. Restroom requirements.
50.84. Enforcement and inspections.
50.85. Approval of plans.
50.86. Variances.
MISCELLANEOUS PROVISIONS
50.91. High rise building.
50.92. Historic building.
50.93. Special stage regulations.
50.94. Fixed seating.Authority The provisions of this Chapter 50 issued under act of April 27, 1927 (P. L. 465, No. 299) (35 P. S. § § 12211235), unless otherwise noted.
Source The provisions of this Chapter 50 adopted May 18, 1984, effective May 19, 1984, 14 Pa.B. 1765, unless otherwise noted.
Notes of Decisions Deference to Agency
Where an administrative agency has interpreted its own regulations, that interpretation will be given controlling authority unless it is plainly erroneous or inconsistent with underlying legislation. There is no error in the Boards determination of violations, and its order is affirmed. Bologna v. Department of Labor and Industry, 816 A.2d 407 (Pa. Cmwlth. 2003), appeal denied 830 A.2d 976 (Pa. 2003).
Single Family Residences
Although the Department of Labor and Industry Industrial Board did not have jurisdiction over single family residences, the Department could enforce the Fire and Panic Act (35 P. S. 12211235), against a tax collector who maintained a public office in the residence. Gnarra v. Department of Labor and Industry, 658 A.2d 844 (Pa. Cmwlth. 1995).
Cross References This chapter cited in 7 Pa. Code § 82.17 (relating to safetyfire prevention and egress); 7 Pa. Code § 139.42 (relating to structures); 12 Pa. Code § 145.35 (relating to applicability of Fire and Panic Act); 22 Pa. Code § 31.43 (relating to buildings and equipment); 34 Pa. Code § 11.85 (relating to applicable provisions of other regulations); 34 Pa. Code § 47.125 (relating to stairs); 34 Pa. Code
§ 49.1 (relating to definitions); 34 Pa. Code § 49.2 (relating to jurisdiction and effective dates); 34 Pa. Code § 49.3 (relating to submission of plans); 34 Pa. Code § 49.5 (relating to certification of plans); 34 Pa. Code § 49.8 (relating to fees for building-plan examinations); 34 Pa. Code § 49.9 (relating to field inspection); 34 Pa. Code § 49.12 (relating to notice of violation and order to correct); 34 Pa. Code § 50.21 (relating to definitions); 34 Pa. Code § 50.24 (relating to exit doors and exit access doors); 34 Pa. Code § 50.92 (relating to historic building); 34 Pa. Code § 60.8 (relating to field inspection); 34 Pa. Code § 60.33 (relating to buildings); 55 Pa. Code § 5200.47 (relating to other applicable regulations); 55 Pa. Code § 5210.56 (relating to other applicable regulations); and 55 Pa. Code § 5320.54 (relating to seclusion and restraints).
OCCUPANCY GROUP
§ 50.1. Occupancy groups.
(a) Class of building. The Department will classify each building into one or more of the following occupancy groups according to the building use and the characteristics of the occupants.
(b) Group AAssembly. Buildings primarily used or designed for the purpose of assembly of persons for amusement, entertainment, worship, transportation, recreation, sports, military drilling, dining or similar purposes shall be classified as Group AAssembly Occupancies. Group A is divided into the following division:
Division Capacity A-1 (Chapter 51) 501 or more A-2 (Chapter 52) 101 thru 500 A-3 (Chapter 53) 4 thru 100 (c) Group BEducational. Buildings primarily used or designed for the purpose of education or instruction shall be classified as Group BEducational Occupancies. Schools for business or vocational training shall be classified in the same occupancies and conform to the same requirements as the trade, vocation or business being taught. Nursery schools, day care centers, group day care homes and the like shall be classified as B occupancies. However, they may be housed in a building which has an A, C-1 or C-2 occupancy permit without submission of plans or approval as a B occupancy. Group day care homes and family day care homes may use the C-3 regulations for occupancies of eight or less children without a B occupancy approval. See Chapter 54 (relating to Group BEducational).
(d) Group CGroup habitation. Buildings primarily used or designed for the purpose of habitation by four or more persons shall be classified as Group CGroup Habitation. Group C is divided into the following divisions:
(1) Division C-1. Health care institutions include buildings that provide sleeping facilities for four or more persons who are mostly incapable of self-preservation because of physical or mental illness or disease, or persons convalescing from physical or mental illness or disease. Hospitals, sanitariums, nursing homes, convalescent homes, rest homes, and the like shall be classified as health care institutions. Personal care homes licensed by the Department of Public Welfare will not be considered health care institutions. Health care institutions shall comply with the following:
(i) Health care institutions which have plans approved by the Department after May 19, 1986, shall comply with NFPA-101, Life Safety Code, 1985 Edition published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.
(ii) Health care institutions or portions of health care institutions which have had plans approved by the Department from June 1, 1976, to May 19, 1986, shall be considered in compliance with this chapter as long as compliance is maintained in accordance with the provisions in force on the date of approval by the Department.
(iii) Health care institutions or portions of health care institutions which complied on May 31, 1976, with the requirements of NFPA-101, Life Safety Code, 1967 Edition will be considered in compliance with this chapter as long as compliance is maintained in accordance with NFPA-101, Life Safety Code, 1967 Edition published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.
(iv) Plan approval and field inspections for health care institutions, Division C-1, are conducted by the Department of Health.
(2) Division C-2. This division applies to a building, or a part thereof, where the occupants are in group habitation and are not included under Division C-1, C-3, C-4 or C-5. Hotels, apartment buildings, multiple dwellings, dormitories, lodging houses, orphanages, childrens residential institutions, large personal care homes, group homes, group foster homes, and the like, shall be in this classification. See Chapter 55 (relating to Division C-2).
(3) Division C-3. This division applies to a building which only has a single living unit where four through eight residents are in group habitation. Small personal care homes, dormitories, lodging houses, orphanages, childrens residential institutions, group homes, group foster homes, and the like having four through eight residents shall be in this classification. See Chapter 56 (relating to Division C-3).
(4) Division C-4. This division applies to apartment units which qualify for a single means of egress. See Chapter 57 (relating to Division C-4).
(5) Division C-5. This division applies to a building, or a part thereof, where the occupants are in group habitation, and are mostly incapable of self-preservation, because they are under restraint. Prisons, jails, reformatories, houses of correction and the like shall be in this classification. C-5 occupancies which have plans approved on or after November 30, 1998, shall comply with Chapters 3, and 14, and all other sections specifically referred to in Chapters 3 and 14 of NFPA-101, Life Safety Code, 1997 Edition published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.
(e) Group DCommercial, Office, Industrial. Buildings primarily used or designed for the purpose of commercial, storage, office or other like purposes shall be classified as Group DCommercial, Office, Industrial Occupancies. Group D is divided into the following divisions:
(1) Division D-O (ordinary occupancy) includes occupancies involving the manufacture, assembling, warehousing, use, sale or storage of combustible but not highly flammable products and materials and buildings used for offices and the like. See Chapter 58 (relating to Division D-O).
(2) Division D-H (hazardous occupancies) includes occupancies involving highly combustible, explosive or unstable products or materials that constitute a special fire, life or toxic hazard because of the forms, characteristics or volume of the materials used. A building, structure or a part thereof used for storage, warehousing, manufacturing, processing, use or sale of highly combustible products or materials, including the following and those of equal fire and life hazard shall be classified under D-H hazardous occupancies. See Chapter 59 (relating to Division D-H).
(i) Chemicals which pose serious flame or explosive hazards upon coming into contact with water or moisture, such as aluminum powder, calcium carbide, red phosphorous, metallic sodium, metallic potassium, sodium peroxide, calcium phosphide, yellow phosphorous and metallic magnesium powder.
(ii) Processes which produce dust, lint or other particles or matter liable to instantaneous ignition or explosion.
(iii) Ammonia, chlorine, phosgene, carbon bisulphide and other toxic irritants or corrosive and fume hazard gases such as acetylene, ether, ethyl chloride, ethylene, liquified hydrocarbons, ethyl chloride gas and similar gases.
(iv) Naptha, ether, benzol, styrene, butadiene, collodion, ethyl, acetate, amyl acetone, amyl alcohol, kerosene, turpentine, petroleum paint, including paint mixing and spraying rooms, varnish, dryer, gasoline, alcohol, oil in bulk quantities and similar highly inflammable liquids. Paint spray booth approved by the Department will be classified as D-O occupancies.
(v) Manufacture and processing of imitation leather, paint and other pyroxylin products.
(vi) Storage of nitrocellulose, or products composed in whole or in part of nitrocellulose or similar flammable materials, such as films, combs, pens.
(vii) Hydrocloric, nitric, sulphuric and hydrofluoric acids.
(viii) Asphalt, tar pitch, resin, waxes and fats, either alone or combined with other materials.
(ix) Flammable fibrous materials such as hay, straw, broomcorn, hemp, tow, jute, sisal, excelsior, kapok, hair, oakum, and the like.
(x) Processing or storing of artificial flowers, matches, mattresses, rubber, cork, brooms, carpet linings, paper, pasteboard, feathers, cotton, including cotton rag sorting rooms, shoddy mills, oil refineries, distilleries, sugar refineries, cereal, flour, grist and starch mills, rendering plants, drying rooms, and occupancies of equal fire and life hazard.
Source The provisions of this § 50.1 amended December 26, 1986, effective December 27, 1986, 16 Pa.B. 4973; amended November 27, 1998, effective November 28, 1998, 28 Pa.B. 5867. Immediately preceding text appears at serial pages (211213) to (211214) and (207379) to (207380).
Notes of Decisions The guests of a bed and breakfast were residents for purposes of defining the use of the property and the building was used primarily as a bed and breakfast establishment. Orth v. Department of Labor and Industry, 588 A.2d 113 (Pa. Cmwlth. 1991) appeal denied 596 A.2d 801 (Pa. 1991).
Cross References This section cited in 34 Pa. Code § 49.2 (relating to jurisdiction and effective dates).
§ 50.2. Occupancy separations and mixed occupancies.
When a structure contains two or more occupancy classes, the occupancy classes shall be governed in one of the following manners:
(1) Separation. When each occupancy class is separated from all other occupancy classes by 2-hour fire walls, each portion thus separated shall be considered a separate building, and limitations for separate buildings shall govern.
(2) Mixed occupancy. Structures with more than one occupancy class which are not separated shall be considered mixed occupancies and shall be governed by the most restrictive of the various limitations of the occupancies.
§ 50.3. Prohibited occupancy mixtures.
Group D-H, Hazardous Occupancies, shall not be permitted in the same structure housing Group A, B or C occupancies.
CONSTRUCTION TYPES
§ 50.11. Construction tables.
(a) Fireresistive construction. Fireresistive construction shall be the type of construction in which the walls, floors, roof and structural members are steel, iron, masonry, concrete or other noncombustible materials meeting all of the requirements of this chapter and having a minimum fireresistive rating as indicated in the construction table.
CONSTRUCTION TABLE
Component
DescriptionMinimum Fireresistive
RatingWALLS Exterior bearing walls 3-hour Noncombustible Exterior panel and curtain walls 1-hour Noncombustible PARTITIONS Bearing partitions 2-hour Noncombustible (1 1/2-hour B Label door assemblies) Nonbearing partitions 1-hour Noncombustible (3/4-hour C Label door assemblies) Partitions enclosing stairs and other vertical openings 2-hour Noncombustible (1 1/2-hour B Label door assemblies) Partitions enclosing exit access corridors 1-hour Noncombustible (3/4-hour C Label door assemblies) COLUMNS Supporting Masonry 3-hour Noncombustible Other 3-hour Noncombustible Supporting roofs only 2-hour Noncombustible GIRDERS AND TRUSSES Supporting masonry walls 3-hour Noncombustible Other 3-hour Noncombustible Supporting roofs only 1-hour Noncombustible FLOOR PANELSIncluding beams and joists 2-hour Noncombustible ROOF PANELSIncluding beams and joists 1-hour Noncombustible
EXCEPTIONS TO CONSTRUCTION TABLE
1. Structural steel and iron members which are used exclusively for elevators and are not part of the structural frame of the building may be unprotected.
2. Fire protective covering may be omitted from structural steel roof structures and members of concrete roof structures of buildings where every part of the roof structure is 20 feet or more above any floor and 10 feet above any balcony or gallery for A, B and C occupancy groups.
3. Nonbearing partitions subdividing an area of 10,000 square feet or less and occupied by a single tenancy may be of fire-retardant treated wood or metal panels without a fireresistive rating.
4. Bays, porches, exterior balconies, and any projections shall be constructed of noncombustible materials.
5. Penthouses and all other roof structures shall be considered part of the next lower story. Where the exterior wall of a penthouse is recessed five feet or more from the next lower storys exterior wall and the exterior wall of the next lower story is required to have a fireresistive rating greater than 1 1/2 hours, the penthouse walls may be constructed of noncombustible materials with a minimum rating of 1 1/2 hours.
6. Panel walls of noncombustible construction attached to the structural frame may be used when no undue hazard is deemed to exist.
(b) Noncombustible construction. Noncombustible construction shall be the type of construction in which all structural members including walls, floors, roofs and their supports are steel, iron, masonry, concrete, or other noncombustible materials having a minimum fireresistive rating as indicated in the construction table.
CONSTRUCTION TABLE
Component
DescriptionMinimum Fireresistive
RatingWALLS Exterior bearing walls Noncombustible Exterior panel and curtain walls Noncombustible Penthouse enclosure walls Noncombustible PARTITIONS Bearing partitions Noncombustible Nonbearing partitions Noncombustible Partitions enclosing stairs and other vertical openings 1-hour Noncombustible (3/4-hour C Label fire door assemblies) Partitions enclosing exit access corridors 1-hour Noncombustible COLUMNS Supporting Masonry Noncombustible Other Noncombustible Supporting roofs only Noncombustible GIRDERS AND TRUSSES Supporting masonry walls Noncombustible Other Noncombustible Supporting roofs only Noncombustible FLOOR PANELSIncluding beams and joists Noncombustible ROOF PANELSIncluding beams and joists Noncombustible
EXCEPTIONS TO CONSTRUCTION TABLE
1. Nonbearing partitions subdividing an area and occupied by a single tenancy may be of fire-retardant treated wood or metal panels without a fireresistive rating.
2. Bays, porches, exterior balconies, and any projections may be constructed of noncombustible materials, or exterior fire-retardant treated wood.
3. Panel walls of fire-retardant treated wood attached to the structural frame may be used when no undue hazard is deemed to exist.
4. Roof construction, including beams and joists may be fire-retardant treated wood.
(c) Protected heavy timber. Protected heavy timber shall be the type of construction in which the exterior walls and fire walls are of masonry, reinforced concrete, or other approved noncombustible materials meeting the requirements of this chapter and having a fireresistive rating as indicated in the construction table. Heavy timber members of the following minimum nominal sizes may be used as an alternative to the construction table without meeting the minimum fireresistive rating.
Columns 8" x 8" Trusses supporting floors 6" x 6" Trusses supporting roofs only 4" x 6" Girders supporting floors 8" x 10" Girders supporting roofs only 6" x 10" Beams supporting floors 6" x 10" Beams supporting roofs only 4" x 8" Floor panels 3" Roof panels 2"
CONSTRUCTION TABLE
Component
DescriptionMinimum Fireresistive
RatingWALLS Exterior bearing walls 2-hour Noncombustible Exterior panel and curtain walls 2-hour Noncombustible PARTITIONS Bearing partitions 1-hour Noncombustible (3/4-hour C Label door assemblies) Nonbearing partition 1-hour Noncombustible (3/4-hour C Label door assemblies) Partitions enclosing stairs and other vertical openings 1-hour Noncombustible (3/4-hour C Label fire door assemblies) Partitions enclosing exit access corridors 1-hour Noncombustible (3/4-hour C Label door assemblies) COLUMNS Supporting Masonry 2-hour Noncombustible Other 2-hour Noncombustible Supporting roofs only 1-hour Noncombustible GIRDERS AND TRUSSES Supporting masonry walls 1-hour Noncombustible Other 1-hour Noncombustible Supporting roofs only 1-hour Noncombustible FLOOR PANELSIncluding beams and joists 1-hour Noncombustible ROOF PANELSIncluding beams and joists 1-hour Noncombustible
EXCEPTIONS TO CONSTRUCTION TABLE
1. Timber arches or trusses may be used to support roof loads. The framing members shall be of not less than 4 inches by 6 inches nominal dimensions, except that spaced members may be composed of two or more pieces, each of not less than three inch nominal thickness when blocked solidly throughout their intervening spaces or when such spaces are tightly closed by a continuous wood cover plate of not less than 2 inch nominal thickness secured to the underside of the members. Splice scabs shall be not less than 3 inch nominal thickness. When protected by approved automatic sprinklers under the roof deck, the framing members may be reduced to not less than 3 inch nominal thickness.
2. Floors may be constructed of splined or tongue and groove plank of not less than 3 inch nominal thickness, covered with 1 inch flooring laid crosswise or diagonally or may be of laminated construction consisting of planks of not less than 4 inch nominal width, laid on edge and spiked together at intervals of 18 inches and covered with 1 inch flooring. Laminated floors shall be laid with staggered joints and shall not be spiked to the supporting girders.
3. Structural steel and iron members which are used exclusively for elevators and are not part of the structural frame of the building may be unprotected.
4. Fire protective covering may be omitted from structural steel roof structures and members of concrete roof structures of buildings where every part of the roof structure is 20 feet or more above any floor and 10 feet above any balcony or gallery for A, B and C occupancy groups.
5. Nonbearing partitions subdividing an area of 10,000 square feet or less and occupied by a single tenancy may be of fire-retardant treated wood or metal panels without a fireresistive rating.
6. Bays, porches, exterior balconies, and any projections shall be constructed of noncombustible materials.
7. Penthouses and all other roof structures shall be considered part of the next lower story. Where the exterior wall of a penthouse is recessed five feet or more from the next lower storys exterior wall and the exterior wall of the next lower story is required to have a fireresistive rating greater than 1 1/2 hours, the penthouse walls may be constructed of noncombustible materials with a minimum rating of 1 1/2 hours.
8. Panel walls of noncombustible construction attached to the structural frame may be used when no undue hazard is deemed to exist.
(d) Ordinary construction. Ordinary construction shall be the type of construction in which the exterior walls are of masonry, concrete or other noncombustible material meeting the requirements of this chapter and having a minimum fireresistive rating as indicated in the construction table. Interior framing may be partially or wholly of wood.
CONSTRUCTION TABLE
Component
DescriptionMinimum Fireresistive
RatingWALLS Exterior bearing walls 2-hour Noncombustible Exterior panel and curtain walls Noncombustible Penthouse enclosure walls 2-hour Noncombustible PARTITIONS Bearing partitions None Nonbearing partitions None Partitions enclosing stairs and other vertical openings 1-hour (3/4-hour C Label fire door assemblies) Partitions enclosing exit access corridors 1-hour (3/4-hour C Label fire door assemblies) COLUMNS Supporting masonry None Other None Supporting roofs only None GIRDERS AND TRUSSES Supporting masonry walls None Other None Supporting roofs only None FLOOR PANELSIncluding beams and joists None ROOF PANELSIncluding beams and joists None
EXCEPTIONS TO CONSTRUCTION TABLE
1. Structural steel and iron members which are used exclusively for elevators and are not part of the structural frame of the building may be unprotected.
2. Firestopping shall be provided in all walls at each floor level to prevent the spread of fire. Horizontal concealed spaces shall be provided with draftstopping each 3,000 square feet. Draftstopping and firestopping materials shall be not less than 1/2 inch gypsum board, 3/8 inch plywood or other equivalent material.
3. No wood framing shall be placed within two inches of the outside of chimneys. This distance may be reduced to 1/2 inch if the members are faced to their full depth with approved insulating material not less than 1/4 inch thick. No wood framing shall be placed within four inches of the backwall of any fireplace. Header beams supporting trimmer arches of fire places shall be not less than 20 inches from the face of the chimney breast.
4. All wood shingles shall be pressure treated to meet the requirements for Class C roof covering in accordance with the Standard Test ASTM E-180 Test for Roof Covering including the weathering test.
5. Solid core wood doors equal to or greater than a 20 minute fireresistive rating may be used for corridor partitions. These doors shall be self-closing and have positive latching.
(e) Wood frame construction. Wood frame construction shall be the type of construction in which structural members and their support are constructed of wood or are dependent upon wood for support and having a minimum fireresistive rating as indicated in the construction table.
CONSTRUCTION TABLE
Component
DescriptionMinimum Fireresistive
RatingWALLS Exterior bearing walls None Exterior panel and curtain walls None Penthouse enclosure walls None PARTITIONS Bearing partitions None Nonbearing partitions None Partitions enclosing stairs and other vertical openings 1-hour (3/4-hour C Label fire door assemblies) Partitions enclosing exit access corridors 1-hour COLUMNS Supporting Masonry None Supporting roofs only None General support None GIRDERS AND TRUSSES Supporting masonry walls None Other None Supporting roofs only None FLOOR PANELSIncluding beams and joists None ROOF PANELSIncluding beams and joists None
CONSTRUCTION TABLE NOTES
1. Firestopping shall be provided in all walls at each floor level to prevent the spread of fire. Horizontal concealed spaces shall be provided with draftstopping each 3,000 square feet. Draftstopping and firestopping materials shall be not less than 1/2 inch gypsum board, 3/8 inch of plywood or other equivalent material.
2. All wood shingles shall be pressure treated to meet the requirements for Class C roof covering in accordance with the Standard Test ASTM E-180 Test for Roof Covering including the weathering test.
3. Solid core wood doors equal to or greater than 20 minute fireresistive rating may be used for corridor partitions. These doors shall be self-closing and have positive latching.
Cross References This section cited in 34 Pa. Code § 49.1 (relating to definitions); 34 Pa. Code § 50.25 (relating to stair towers); and 34 Pa. Code § 50.43 (relating to classification).
MEANS OF EGRESS
§ 50.21. Definitions.
(a) A means of egress is a continuous and unobstructed way of travel from a point in a building or structure to a safe area of refuge outside of the building or structure. A means of egress consists of three separate parts: the way of exit access, the exit, and the way of exit discharge. A means of egress comprises the vertical and horizontal ways of travel and includes intervening room spaces, doorways, hallways, corridors, passageways, balconies, ramps, stairs, enclosures, lobbies, escalators, horizontal exits, courts and yards.
(b) Exit access is a path of travel which leads to an exit.
(c) Exit is the portion of a means of egress which is separated from other spaces of the building or structure by construction as required in Chapters 49-59 (relating to administrationbuildings; general requirementsbuildings; A-1 assembly; Division A-2 assembly; Division A-3 assembly; Group B educational; Division C-1 health care institutions; Division C-2 hotels, motels, apartment buildings; Division C-3 small group habitation; Division C-4 single exit apartments; Division C-5 prisons, jails, reformatories, and houses of corrections; Division D-O ordinary commercial, industrial, office; and D-H hazardous commercial, industrial, office) to provide a way of travel to the exit discharge.
(d) Exit discharge is the portion of a means of egress between the termination of an exit and a safe area of refuge outside of the building or structure which has direct access to a public street or thoroughfare or an open area with unrestricted access to a public street or thoroughfare.
§ 50.22. Exit accessibility standards.
(a) Either direct access to exits or safe and continous corridors or aisles leading directly to every exit and arranged so as to be conveniently accessible by every occupant shall be maintained and kept unobstructed on all floors of buildings.
(b) Travel distances shall be measured in the following manner:
(1) Exits shall be so arranged that the total length of travel from any point to reach an exit will not exceed 150 feet.
![]()
(2) Exits shall be so arranged that one exit is not more than 200 feet from another exit.
![]()
(3) Dead ends and occupancy areas with access to a single exit shall not exceed 75 feet measured as a radius with the center of the circle being the exit.
![]()
(4) Travel distances may be increased to the following in buildings totally protected by an automatic sprinkler system installed in accordance with NFPA-13, 1983 Edition.
(i) 200 feet from any point to an exit.
(ii) 300 feet between exits.
(iii) 100 feet for dead ends and areas with a single path of egress.
(c) Exit access corridor means a corridor which is separated from all other rooms or spaces by full height partitions (floor to ceiling). Exit access corridors shall lead directly to exits. This definition is not intended to restrict the use of open plan floor arrangements. It is intended to provide protected exit access where floor areas are separated from each other by floor to ceiling partitions.
(d) All means of egress shall be properly illuminated, either naturally or artificially, during all periods of occupancy.
(e) All exits shall be marked by a readily visible sign. Access to exits shall be marked by readily visible signs indicating the direction of travel where the exit or way to reach it is not immediately visible to the occupants.
This section cited in 34 Pa. Code § 51.23 (relating to means of egress capacity); 34 Pa. Code § 52.23 (relating to means of egress capacity); 34 Pa. Code § 53.23 (relating to means of egress capacity); 34 Pa. Code § 54.23 (relating to means of egress capacity); 34 Pa. Code § 55.23 (relating to means of egress capacity); 34 Pa. Code § 56.23 (relating to means of egress capacity); 34 Pa. Code § 57.23 (relating to means of egress capacity); 34 Pa. Code § 58.23 (relating to means of egress capacity); and 34 Pa. Code § 59.23 (relating to means of egress capacity).
§ 50.24. Exit doors and exit access doors.
(a) Doors used in connection with exits, exit discharge or exit access shall be of substantial construction, installed in a workmanlike manner, fitted with reliable hardware and shall be of the side-hinged, vertical hung, swinging type.
(b) Exit, exit access and exit discharge doors shall swing out with the exit travel except that exit access doors from individual rooms need not swing with exit travel when the room occupancy is less than 50 persons.
(c) Doors which lead into the path of travel from other areas shall be located so that they do not encroach more than 8 inches upon the required width of such path of travel when at their full open position.
(d) All exit and exit discharge doors shall be provided with panic hardware or fire exit hardware.
(1) The actuating portion of the panic hardware or fire exit hardware shall be a minimum of 1/2 of the width of the door leaf and shall be mounted between 30 inches to 44 inches above the floor. The latch shall be released when a force not to exceed 15 pounds is applied to the actuating device in the direction of exit travel. No lock or other device which prevents egress shall be permitted on the doors during any period of occupancy.
(2) Main entrance doors do not require panic hardware when the doors are unlocked and ready for use when the building is occupied. Not more than one door or group of doors at one location can be considered as main entrance doors.
(e) All doors shall have a minimum clear width opening of 32 inches. All doors required by Chapters 49-59 (relating to administrationbuildings; general requirementsbuildings; A-1 assembly; Division A-2 assembly; Division A-3 assembly; Group B educational; Division C-1 health care institutions; Division C-2 hotels, motels, apartment buildings; Division C-3 small group habitation; Division C-4 single exit apartments; Division C-5 prisons, jails, reformatories, and houses of corrections; Division D-O ordinary commercial, industrial, office; and D-H hazardous commercial, industrial, office) shall be a minimum of 6 feet, 8 inches in height.
(f) All exterior doors leading to grade shall have a landing at least 3 feet square but in no case may the landing be smaller than the door which it serves.
(g) Stairs shall be provided where the exterior grade is more than 8 inches below the floor level. These stairs shall comply with § 50.26 (relating to intercommunicating stairway).
(h) Every door to a stairway shall have a landing on both sides of the door at least as wide as the stair.
(i) Approved collapsible revolving doors may be used as exits; however, they may not constitute more than 50% of the required exit width. The clear width of the opening, when the doors are in a collapsed position, shall be used in determining the number of units of width to be allowed for each revolving door.
Cross References This section cited in 34 Pa. Code § 50.23 (relating to means of egress capacity); 34 Pa. Code § 51.25 (relating to stair towers); 34 Pa. Code § 52.25 (relating to stair towers); 34 Pa. Code § 53.25 (relating to stair towers); 34 Pa. Code § 54.25 (relating to stair towers); 34 Pa. Code § 55.25 (relating to stair towers); 34 Pa. Code § 56.25 (relating to stair towers); 34 Pa. Code § 57.25 (relating to stair towers); 34 Pa. Code § 58.25 (relating to stair towers); and 34 Pa. Code § 59.25 (relating to stair towers).
§ 50.26. Intercommunicating stairway.
(a) Intercommunicating stairways are stairways which connect two or more floor levels of a building. They may be open to one floor level. They are not required to discharge directly to grade. Intercommunicating stairways shall comply with subsections (b)(q) when used as a required means of egress.
(b) Intercommunicating stairways shall be Class A or Class B types in accordance with the following table:
Class A Stair Class B Stair Minimum clear width in inches 40" 36" Maximum height of riser 7 1/2" 8" Minimum width of tread 10" 9" Maximum angle of stairs in degrees 33° 40° Required handrails
(Each handrail is allowed to project
3" without decreasing the
minimum clear width)Both sides One side under 40" in width, both sides 40" or more in width Maximum vertical distances between landings 9' 12' (c) The minimum width of landings shall be the same width as the stairs they serve. Intermediate landings on straight run stairs shall have a minimum length of 3 feet.
(d) The narrowest width in a stairway or landing serving a stairway shall determine the units of width for the entire stairway.
(e) There shall be no variation in the width of treads or the height of risers in any flight. Variation in height of risers in adjacent flights shall not exceed 1/4 inch. All treads less than 10 inches, as measured horizontally between the face of risers, shall have an effective projection of approximately 1 inch beyond the face of the riser below.
(f) Where material of stair treads and landings is such as to present a danger of slipping, nonskid material shall be applied.
(g) No arrangement of treads known as winders shall be permitted in required exit stairways.
(h) All stairways, landings, balconies, open sided floors, and the like shall have well secured handrails. The clear distance between handrail and wall or other obstruction shall be not less than 1 1/2 inches. Longitudinal rails or balusters or both shall be provided. Balusters shall be spaced not more than 6 inches apart. Longitudinal rails shall not exceed 6 inches measured at right angles to the rails. The lowest rail shall be measured vertically from the tread nosing.
(i) Handrails on stairs shall be not less than 30 inches nor more than 34 inches above the upper surface of the tread, measured vertically to the top of the rail, from a point on the tread 1 inch back from the leading edge.
(j) Handrails shall be provided on any stair landing, balcony, ramp, aisle, and the like located along the edge of open sided floors or mezzanines to prevent falls over the open side. Railings protecting open sides of landings, balconies, mezzanines, and the like shall be at least 42 inches high.
(k) Storage or obstructions of any kind shall not be permitted in stairways.
(l) A door opening into a stairway shall at no point in its swing reduce the required units of width of the stair or landing.
(m) Every door to a stairway shall open onto a landing at least as wide as the stairs.
(n) Doors and frames used in connection with stairways shall be of approved label and be of substantial construction, installed in a workmanlike manner, fitted with reliable hardware of approved label and shall be of the side hinged, swinging type.
(o) Stairway doors shall swing with the exit travel.
(p) Stairway doors shall be provided with panic hardware or fire exit hardware. No lock or other device which prevents egress shall be permitted on such doors during any period of occupancy.
(q) Stairway doors shall be a minimum of 32 inches in width. All doors used in connection with stairways shall be a minimum of 6 feet, 8 inches in height.
Cross References This section cited in 34 Pa. Code § 50.23 (relating to means of egress capacity); 34 Pa. Code § 50.24 (relating to exit doors and exit access doors); 34 Pa. Code § 50.94 (relating to fixed seating); 34 Pa. Code § 53.26 (relating to intercommunicating stairways); 34 Pa. Code § 55.26 (relating to intercommunicating stairways); 34 Pa. Code § 56.26 (relating to intercommunicating stairways); and 34 Pa. Code § 58.26 (relating to intercommunicatng stairways).
§ 50.27. Ramps.
(a) A ramp shall be permitted as a means of egress when it conforms to the following table:
Minimum clear width in inches 40 inches Maximum slope 1 inch per foot (8.33%) Maximum length between landings 30 feet Required handrails Both sides (each handrail is allowed to project 3 inches without
decreasing the minimum clear width)(b) Changes in direction of travel shall be made only at landings.
(c) Ramps which connect two or more floor levels shall comply with the same door, handrail and enclosure requirements as stair towers.
(d) Sloped surfaces of less than 5.0% shall not be considered ramps.
Cross References This section cited in 34 Pa. Code § 51.27 (relating to ramps); 34 Pa. Code § 52.27 (relating to ramps); 34 Pa. Code § 53.27 (relating to ramps); 34 Pa. Code § 54.27 (relating to ramps); 34 Pa. Code § 55.27 (relating to ramps); 34 Pa. Code § 56.27 (relating to ramps); 34 Pa. Code § 57.27 (relating to ramps); 34 Pa. Code § 58.27 (relating to ramps); and 34 Pa. Code § 59.27 (relating to ramps).
§ 50.28. Horizontal exits.
(a) A horizontal exit is a 2-hour fire wall with one or more openings protected by 1 1/2-hour door assemblies which permit passage from one building or structure to another or area of refuge within the same building.
(b) Horizontal exits may constitute no more than 50% of the required units of exit.
(c) Fire walls which serve as horizontal exits shall extend to exterior walls or 2-hour fire walls. They shall not be dependent on any structural members of less than 2-hour fireresistance.
(d) A horizontal exit shall have at least one door which swings with the exit travel from each building section that it serves.
Cross References This section cited in 34 Pa. Code § 51.28 (relating to horizontal exits); 34 Pa. Code § 52.28 (relating to horizontal exits); 34 Pa. Code § 53.28 (relating to horizontal exits); 34 Pa. Code § 54.28 (relating to horizontal exits); 34 Pa. Code § 55.28 (relating to horizontal exits); 34 Pa. Code § 56.28 (relating to horizontal exits); 34 Pa. Code § 58.28 (relating to horizontal exits); and 34 Pa. Code § 59.28 (relating to horizontal exits).
§ 50.29. Escalators.
Escalators used as a means of egress shall conform with all of the following standards:
(1) Maximum uninterrupted vertical travel of one story.
(2) An escalator 24 inches in width or larger shall be considered a maximum of one unit of width.
(3) Escalators shall be of the horizontal tread type.
(4) Escalators shall not exceed 50% of the required units of exit.
VERTICAL OPENINGS
§ 50.31. Vertical openings 9 square feet or more.
Walls and partitions enclosing vertical openings 9 square feet or more shall be constructed as set forth in the following table:
Construction Type Fireresistive Requirement Fire Door Assembly Fireresistive 2-Hour Noncombustible 1 1/2-hour B Label Noncombustible 1-Hour Noncombustible 3/4-hour C Label Protected Heavy Timber 1-Hour Noncombustible 3/4-hour C Label Ordinary 1-Hour 3/4-hour C Label Wood Frame 1-Hour 3/4-hour C Label
Cross References This section cited in 34 Pa. Code § 50.32 (relating to vertical openings less than 9 square feet); 34 Pa. Code § 51.31 (relating to vertical openings); 34 Pa. Code § 52.31 (relating to vertical openings); 34 Pa. Code § 53.31 (relating to vertical openings); 34 Pa. Code § 54.31 (relating to vertical openings); 34 Pa. Code § 55.31 (relating to vertical openings); 34 Pa. Code § 57.31 (relating to vertical openings); 34 Pa. Code § 58.31 (relating to vertical openings); and 34 Pa. Code § 59.31 (relating to vertical openings).
§ 50.32. Vertical openings less than 9 square feet.
Shafts less than 9 square feet in area not complying with § 50.31 (relating to vertical openings 9 square feet or more) shall have enclosing walls or be lined with sheet metal having lock jointed or riveted seams and joints. Combustible material, partitions, and floors through which shafts pass shall be kept at least 3 inches from the metal lining or shall be protected by the equivalent of 3/8 inch of plaster or plaster board. Openings between shafts and the floor construction through which they pass shall be filled with noncombustible material, securely held in place to prevent the passage of fire. Doors opening into the vertical shafts shall be of metal or shall be covered on the shaft side by the equivalent of 1/4 inch of asbestos and not less than 26 gauge steel turned around all edges and securely fastened to the door.
Cross References This section cited in 34 Pa. Code § 51.31 (relating to vertical openings); 34 Pa. Code § 52.31 (relating to vertical openings); 34 Pa. Code § 53.31 (relating to vertical openings); 34 Pa. Code § 54.31 (relating to vertical openings); 34 Pa. Code § 55.31 (relating to vertical openings); 34 Pa. Code § 57.31 (relating to vertical openings); 34 Pa. Code § 58.31 (relating to vertical openings); and 34 Pa. Code § 59.31 (relating to vertical openings).
§ 50.33. Fire door assemblies.
Fire door assemblies in vertical openings shall be self-closing, latching, and normally kept closed. Electromagnetic hold open devices may be approved by the Department where all of the following conditions are met:
(1) Upon release, the door becomes self-closing.
(2) An approved release device is provided, so arranged that upon interruption of electric current, the door will be released.
(3) The release device is so designed that the door may be instantly released manually by some simple and readily obvious operation, and upon release the door becomes self-closing.
(4) The electric current will be positively interrupted by one or more of the following methods:
(i) The operation of an approved automatic sprinkler system which protects the entire building, including both sides of any horizontal exit.
(ii) The operation of an approved automatic fire alarm system installed to protect the entire building.
(iii) By the operation of approved smoke detectors installed in such a way to detect smoke or other products of combustion on either side of the door opening.
Cross References This section cited in 34 Pa. Code § 51.31 (relating to vertical openings); 34 Pa. Code§ 52.31 (relating to vertical openings); 34 Pa. Code § 53.31 (relating to vertical openings); 34 Pa. Code § 54.31 (relating to vertical openings); 34 Pa. Code § 55.31 (relating to vertical openings); 34 Pa. Code § 57.31 (relating to vertical openings); 34 Pa. Code § 58.31 (relating to vertical openings); and 34 Pa. Code § 59.31 (relating to vertical openings).
§ 50.34. Exterior openings.
Exterior openings in vertical shafts which require a minimum 1-hour fire-resistive rating shall be of incombustible construction with all glazed portions being 1/4 inch wire glass in steel frames when such openings are within 10 feet of any other openings in a vertical or horizontal plane.
Cross References This section cited in 34 Pa. Code § 51.31 (relating to vertical openings); 34 Pa. Code § 52.31 (relating to vertical openings); 34 Pa. Code § 53.31 (relating to vertical openings); 34 Pa. Code § 54.31 (relating to vertical openings); 34 Pa. Code § 55.31 (relating to vertical openings); 34 Pa. Code § 57.31 (relating to vertical openings); 34 Pa. Code § 58.31 (relating to vertical openings); and 34 Pa. Code § 59.31 (relating to vertical openings).
INTERIOR FINISH
§ 50.41. Definitions.
Interior finish is the exposed interior surfaces of a building. Paint, wallpaper not more than 1/28 inch thick and similar wall finishes having no greater fire hazard than wallpaper shall not be considered interior finishes. Decorations and furnishings are not considered interior finishes.
§ 50.42. Basic material used.
The classification of interior finish materials shall be that of the basic material used without regard to subsequently applied paint or wallpaper not more than 1/28 inch thick.
§ 50.43. Classification.
(a) NFPA Standard. Interior finish materials shall be classified in accordance with NFPA Standard 255, tests of surface burning characteristics of building materials, 1979 Edition as listed in this section.
(b) Class A Interior Finish. Flame Spread 0-25 includes any material classified at 25 or less on the test scale. Any element thereof when so tested shall not continue to propagate fire.
(c) Class B Interior Finish. Flame Spread 26-75 includes any material classified at more than 25 but not more than 75 on the test scale.
(d) Class C Interior Finish. Flame Spread 76-200 includes any material classified at more than 75 but not more than 200 on the test scale.
(e) Exposed portions of structural wood members complying with the size requirements in § 50.11(c) (relating to construction tables) shall not be considered interior finishes.
MANUAL AND AUTOMATIC FIRE ALARM SYSTEMS
§ 50.51. Manual system.
(a) A manual fire alarm system is a system that consists of manual pull stations, signaling devices, power source, control panel and other related components which is designed to provide notification to all building occupants.
(b) Manual pull stations shall be installed on each floor including basements, penthouses and equipment rooms. The pull stations shall be installed at each point of egress from a floor area within 5 feet of the exit.
(c) The manual pull stations shall be mounted between 36 inches and 44 inches above the finished floor.
(d) Noncoded, selective coded, or zone coded alarm systems may be installed. When coded systems are used, there shall be a minimum of four rounds of a four-pulse or more code that is indicative of the area of alarm initiation. The alarm system shall be installed in such a way that simultaneous alarms from different stations or zones will not cause a confused or jumbled code. The maximum number of different audible codes in any one facility shall be 150 except where the installation means would permit five or more simultaneously received alarms to sound successively without loss of a round from any alarmed station.
(e) All types of manual pull stations shall be wired and connected in such a way so that a single open will only indicate a trouble condition and not initiate a general alarm.
This section cited in 34 Pa. Code § 50.51 (relating to manual system); and 34 Pa. Code § 50.52 (relating to automatic system).
§ 50.56. Testing new equipment.
(a) New systems tests. Before a fire alarm system is placed into service, all equipment, including new equipment added to existing systems, shall be thoroughly tested for proper operation. Documentation shall be made of the tested devices and be made available to representatives of the Department for their review.
(b) Method of testing new equipment. The testing of new fire alarm systems shall include the operation of all manual pull stations, automatic fire detectors, audible signalling units, visual signalling units, control panels, annunciators, trouble signals, and required auxiliary function devices. Automatic fire detectors that are destroyed when tested or used shall have a minimum of one such device tested in each zone in such a way to assure proper circuit operations.
Cross References This section cited in 34 Pa. Code § 50.51 (relating to manual system); and 34 Pa. Code § 50.52 (relating to automatic system).
§ 50.57. Fire drills.
Fire drills should be conducted in all buildings required to have a manual or automatic fire alarm system. The drills should include the actuation of any of the alarm initiating devices, operation of signalling units and all required auxiliary functions. Fire drills conducted in hotels, motels and similar buildings are for staff training purposes and general alarms that would cause building evacuation should not be initiated during drills.
(1) Fire drills should be performed a minimum of once every 6 months. All drills should be held during normal occupancy times.
(2) Documentation should be kept of all fire drills indicating the date, time of day, system operation and occupant response remarks. This documentation should include the signature of the person conducting the fire drill.
§ 50.58. Inspection and maintenance of detection devices in apartments.
(a) The owner, or the owners agent, shall inspect the automatic fire alarm devices located in individual apartments every 12 months to ensure that the devices are functioning properly.
(b) The following is the responsibility of the tenant, unless specified otherwise in the lease agreement. The tenant shall:
(1) Inspect and test the operation of the automatic fire alarm device at the beginning of the tenants occupancy and monthly thereafter.
(2) Replace batteries, if necessary, to keep the automatic fire alarm device operable and functioning properly.
(c) The tenant shall notify the owner, or the owners agent, if the automatic fire alarm device is not functioning properly.
(d) The owner, or the owners agent, shall notify tenants of their responsibilities under this section by delineating those responsibilities in the lease or rental agreement, or by written notice at the time the lease or rental agreement is presented to the tenant for signing, or by written notice prior to occupancy or release renewal where there is no written lease agreement.
(e) An owner of a building having one or more apartments who complies with the requirements of these regulations concerning automatic fire alarm systems is not responsible for damage or injury to a person or property due to, or as a result of, the misuse or tampering with the automatic detection device caused by a person other than the owner or the owners agent.
Source The provisions of this § 50.58 adopted August 7, 1992, effective August 8, 1992, 22 Pa.B. 4091.
Cross References This section cited in 34 Pa. Code § 49.2 (relating to jurisdiction and effective dates).
EMERGENCY LIGHTING SYSTEMS
§ 50.61. General requirements.
(a) Approval. All emergency lighting systems installed to provide emergency illumination as required by this chapter shall be approved.
(b) Location. The emergency source of energy for illumination shall be a device installed within the building. Special permission may be granted by the Department to locate the emergency lighting system on the premises when not located within the building. The device shall be either an approved engine generator or approved battery system.
(c) Automatic control. The control of the emergency source shall be fully automatic and not dependent upon the manual operation of any switch or device. The emergency source shall supply power when a loss of normal source power occurs on any phase or line to a panel serving an area requiring emergency lighting due to breaker opening, fuse failure or removal, cable failure or similar conditions.
(d) Control panel functional requirement. Each emergency lighting system shall include an approved control panel for area protection. The control panel shall include low voltage sensing devices (three for three phase and one for one phase systems) capable of detecting a reduction in normal source voltage to approximately 80% of rated source voltage, coded visual indication of the space experiencing the power failure and isolated means for activating the emergency source. A break in any conductor feeding the control panel shall cause a failure indication.
(e) Control panel location. The control panel shall be of an approved type and shall be enclosed in a metal cabinet having a hinged door equipped with an effective lock and catch. The visual indicators of a failure shall be visible with or without opening the cabinet door. A nameplate affixed to the door of the cabinet shall designate the equipment as the area protection control panel. Suitable marking plates shall be provided at visual indicators to enable field marking of areas protected. The control panel shall be securely mounted in a clean dry location where it will be conspicuous and readily accessible at all times. Nonlocking type over-current devices are acceptable in all circuits to the control panel.
(f) Full illumination within 15 seconds. Emergency lighting systems shall provide full illumination within 15 seconds after normal source power failure.
(g) Nameplate. Emergency lighting systems shall be provided with a nameplate setting forth the name of the manufacturer, model number, and such other details as may be specifically mentioned in the special requirements for the different types of equipment. The nameplate shall be securely fastened to the equipment and shall not be removed.
(h) Permissible load. The total connected emergency load shall not be greater than that which the system is designed to carry for a period of 1 hour.
(i) Connection with normal supply. Except unit systems, emergency systems utilizing a device which makes the system inoperative when the building is not occupied shall be connected so that some of the normal circuits necessary for illumination, in each location requiring emergency illumination, cannot be used unless the emergency source is ready for use.
(j) Switches. No protective or disconnecting devices other than the following shall be permitted to be installed in the emergency lighting circuits:
(1) Panelboards for emergency lighting distribution may contain circuit breakers, each of which shall be equipped with a handle locking device to prevent unauthorized operation of the breaker and disconnection of the circuit. The panelboards shall be clearly marked with the legend emergency lighting.
(2) Location disconnecting devices, such as wall switches, designed to disconnect the emergency supply from rooms which are not being used shall also disconnect the entire normal supply to the rooms, but they may not cut off the emergency source from the hallways, stairways, ramps and similar passageways leading to outside building exits.
(k) Submission and approval of plans. No device or system required by this chapter shall be installed until floor plans or sketches have been filed with and approved by the Department. The plans or sketches shall be in triplicate and shall show the proposed location of the equipment, the location of all exit or other lights connected to the emergency system and other information which the Department may request. The Department approval denotes approval only of the location of emergency fixtures throughout the building. The information required by this subsection may be included on the general building plans and submitted for approval.
(l) Testing required. Systems shall be proved with a test switch to simulate a power failure to the emergency throwover switch or equipment. A complete test of all emergency lighting systems and inspection of all circuits for satisfactory operation shall be made at least once each week, except that when buildings or rooms are used less than once a week, tests may be made within 1 hour prior to the opening of the room or building on each day of use. A record of tests shall be maintained and shall be available for inspection. No building or room within the scope of this chapter shall be used unless both regular and emergency sources of illumination are available.
(m) Interlocks required. Emergency throwover switches and equipment shall be interlocked so that no line or phase of the emergency source of supply shall be connected to a line or phase of the normal supply. Grounded neutrals may be interconnected.
(n) Transfer switch capability to withstand high-fault currents. The transfer switch or switchgear shall be capable of carrying the maximum fault current available on the load side of the transfer switch or switchgear for the time required for circuit to be cleared of the fault current by fuses or circuit breakers on the service sides of the transfer switch or switchgear. The ability of the switch to carry rated current within recognized temperature rise limits shall be unimpaired after being subjected to one operation at the maximum fault current available.
(o) Minimum intensity of illumination. Emergency lighting systems, other than unit systems utilizing floor or spot light type of distribution, shall produce and maintain for at least 1 hour a minimum intensity of illumination, measured on a horizontal plane 30 inches above the floor as follows:
(1) An intensity of 5/10 of a footcandle at exit doors, hallways, corridors, passageways, stairways, runways, ramps and the like, leading to the outside building exits.
(2) An intensity of 25/100 of a footcandle at other locations requiring emergency lighting.
(3) An intensity of 15/100 of a footcandle, with special permission from the Department, in theaters and motion picture theaters where arrangements have been made to automatically continue the performance even though a power failure has occurred.
(p) Where unit storage battery systems utilizing flood or spot light type of distribution are used, the distance between adjacent units shall not exceed 50 feet. The projectors shall be directed towards the exits and located so as to provide distribution of light over the entire floor area. Glare and sharp shadows shall be held to a minimum. The minimum total operating lamp load measured after 1 hour of battery operation shall be in accordance with the following:
(1) A rating of 1/10 watt per square foot of floor area of hallways, passageways, stairways, ramps, corridors, and the like, leading to the outside building exits.
(2) A rating of 5/100 watt per square foot at other locations requiring emergency lighting.
Cross References This section cited in 34 Pa. Code § 50.62 (relating to storage battery systems); 34 Pa. Code § 50.63 (relating to unit systems); and 34 Pa. Code § 50.64 (relating to internal combustion engine generator systems).
§ 50.62. Storage battery systems.
(a) Types of batteries permitted. When lead acid storage batteries are provided as the emergency source of supply, they shall be designed and constructed to adequately meet the requirements of emergency lighting service and shall be contained in sealed glass or heat resistant plastic jars except as otherwise noted in this chapter. The cells shall be assembled with an electrolyte having full charge specific gravity of 1.200-1.225.
(b) Battery charging equipment. Storage battery emergency lighting systems shall be equipped with a device for maintaining the batteries in a fully charged condition. No switch which may render thisdevice ineffective is permitted. Each time the emergency lighting system is used because of the failure of the main supply, a charge at maximum rate shall be given to the battery immediately. The same rate of charge shall be given to the battery as often as necessary to assure its maintenance in a fully charged condition. The charging device shall be capable of placing the batteries in a state of full charge with 12 hours after restoration of power following a power failure.
(c) Care of batteries. Storage batteries used in emergency lighting systems shall be mounted in a well ventilated room or cabinet, and will be maintained at a temperature of not less than 65° F. The mounting of the cells shall be of ample strength and rigidity to carry the weight without appreciable sagging. Batteries shall not be located in places where they would be subject to deterioration through dampness.
(d) Voltmeter required. Storage battery systems shall be provided with a voltmeter having a guaranteed accuracy of 1% of full scale, except that a voltmeter having a guaranteed accuracy of 2% of full scale may be used if the voltmeter received a special calibration at the normal float charge value so that the accuracy of indication at this point on the scale is not less than 1.0% of full scale value. The voltmeter shall indicate the voltage of the battery at all times.
(e) Nameplate. The nameplate required by § 50.61 (g) (relating to general requirements) shall also contain the final rated voltage of the battery under load at the end of the one hour period, the specific gravity of the electrolyte when the batteries are fully charged, capacity of system in watts, rated nominal voltage and current.
(f) Capacity. The capacity of the storage battery when fully charged shall be sufficient to carry the connected emergency load for a period of not less than 1 hour with a final voltage not less than 87% of the nominal lamp voltage.
(g) Trouble indications. Storage battery systems shall be provided with a device that gives an audible and visual signal when there is an open circuit between the trickle charger and the battery. Such signals shall be located so that they may be seen and heard by a responsible person. In place of the signals the voltmeter required in subsection (d) shall have plainly marked zones as follows:
(i) A marked zone to indicate proper trickle (float) charge voltage.
(ii) A marked zone to indicate a failure of the trickle charger or that the battery is discharging into the emergency lighting circuit.
(iii) A marked zone to indicate during normal float charge operation that there is an open circuit between the trickle charger and battery.
(h) Hydrometer. The manufacturer of storage battery emergency lighting systems shall supply with each device a hydrometer and directions for its use in order that the owner may be in a position to test the specific gravity of the electrolyte. Such a test shall be made at least once every 2 weeks, a record of test shall be maintained and shall be available for inspection.
(i) Other use of batteries. The batteries of emergency lighting systems may not be used for any other purpose unless approved by the Department.
(j) Modified low voltage systems. Battery operated emergency lighting systems, not less than 12 volts or more than 24 volts may be used with the special approval of the Department when the emergency lighting illumination required does not necessitate a battery capacity in excess of 250 watts at the rated voltage for a period of 1 hour.
§ 50.63. Unit systems.
(a) Limitations. Unit battery systems shall provide the required intensity of illumination for a minimum period of 1 hour.
(b) Cabinet design. Emergency lighting units of this class shall be compact and self-contained. Batteries, relays, charging equipment and controls shall be assembled in a substantial metal cabinet. The cabinet shall be well ventilated and designed so that the equipment can be easily maintained. The emergency lighting load shall be connected automatically to the battery in the event of power failure.
(c) Type of batteries. Lead acid batteries shall be the glass jar or the heat resistant plastic jar type or other approved types assembled with 1.200-1.225 specific gravity, full charge electrolyte. At least one pilot cell shall contain a suitable means for indicating the approximate state of charge, which shall be visible from outside the unit case. Other types of batteries may be approved.
(d) Battery charger. Units shall contain a suitable dry disc type of charger capable of charging the battery at a high rate and also at a suitable maintenance of trickle rate. The high rate charge shall be capable of replacing the maximum charge taken out in 1 hour emergency discharge period within 12 hours. The unit shall be designed to provide for automatic high rate charging and restoration to trickle rate. After power failure or when the battery becomes discharged so that the unit cannot provide 1 hour of illumination of required intensity, the battery shall be charged at a high rate, until it becomes fully charged at which time the charging rate shall be reduced to the trickle rate. No device which could render the charger ineffective shall be permitted.
(e) Test switch. All units shall be equipped with a suitable test switch mounted outside of the cabinet and connected to simulate a power failure to the unit.
(f) Signals. All units shall be equipped with a visual signal to indicate when the battery is being charged at the high rate. Units equipped with a switch to disconnect the emergency lamp load in the event of power failure when the building is not occupied shall have a visual signal to indicate when the switch is in the normal position and the equipment is ready to provide emergency lighting.
(g) Wiring and mounting. All units and lamps connected remote from the units shall be permanently mounted. Units shall be mounted so that they may be readily tested, inspected, and serviced and shall be maintained in satisfactory working condition. When remote lamps are used, wiring shall be of sufficient diameter to provide not less than the minimum required illumination. No switch shall be used to cut off the remote lamps.
(h)&n