Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 488 (January 27, 2024).

34 Pa. Code § 50.56. Testing new equipment.

§ 50.56. Testing new equipment.

 (a)  New systems tests. Before a fire alarm system is placed into service, all equipment, including new equipment added to existing systems, shall be thoroughly tested for proper operation. Documentation shall be made of the tested devices and be made available to representatives of the Department for their review.

 (b)  Method of testing new equipment. The testing of new fire alarm systems shall include the operation of all manual pull stations, automatic fire detectors, audible signalling units, visual signalling units, control panels, annunciators, trouble signals, and required auxiliary function devices. Automatic fire detectors that are destroyed when tested or used shall have a minimum of one such device tested in each zone in such a way to assure proper circuit operations.

Cross References

   This section cited in 34 Pa. Code §  50.51 (relating to manual system); and 34 Pa. Code §  50.52 (relating to automatic system).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.