Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 488 (January 27, 2024).

34 Pa. Code § 55.71. Fire extinguishers.

EXTINGUISHERS AND SPRINKLER SYSTEMS


§ 55.71. Fire extinguishers.

 (a)  Fire extinguishers with a minimum 2-A rating shall be provided as follows:

   (1)  Apartment units—one per unit.

   (2)  Other C-2 occupancies—one for each 3,000 square feet or fraction thereof.

 (b)  There shall be a minimum of one fire extinguisher per floor including basement.

 (c)  Fire extinguishers shall be located so that it shall not be necessary to travel more than 100 feet in any direction to reach the nearest unit.

 (d)  A fire extinguisher with a minimum 10-B rating shall be provided in each kitchen.

 (e)  Where fire extinguishers are installed in a closet or recessed in a wall or obscured from view, there shall be provided adjacent thereto a constant blue light of not less than 25 watt capacity. Fire extinguishers in individual apartments need not comply with this subsection.



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.